Plan Review Notes
Plan Review Notes For Permit 17120219
Permit Number 17120219
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-12-08 11:00:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED FIRE ALARM APPEARS TO BE A STAND ALONE
 SEPARATE SYSTEM. THIS IS NOT A STAND ALONE BUILDING. IT
 IS A PART OF A PLAZA AND SERIES OF STORES. A FIRE ALARM
 IN THIS SPACE SHALL ALERT ADJACENT SPACES.
  
 ACCORDING TO A PREVIOUSLY APPROVED PERMIT AND INSTALLED
 SYSTEM,16110614, THIS SYSTEM IS TO BE TIED INTO THE
 PLAZA FIRE ALARM.
  
 PLEASE CORRECT PROVIDE REVISIONS CONSISTENT WITH
 PREVIOUS FIRE ALARM PERMITTING AND FUNCTION.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  