Plan Review Notes For Permit 17120219 |
Permit Number |
17120219 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-08 11:00:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED FIRE ALARM APPEARS TO BE A STAND ALONE | | SEPARATE SYSTEM. THIS IS NOT A STAND ALONE BUILDING. IT | | IS A PART OF A PLAZA AND SERIES OF STORES. A FIRE ALARM | | IN THIS SPACE SHALL ALERT ADJACENT SPACES. | | | | ACCORDING TO A PREVIOUSLY APPROVED PERMIT AND INSTALLED | | SYSTEM,16110614, THIS SYSTEM IS TO BE TIED INTO THE | | PLAZA FIRE ALARM. | | | | PLEASE CORRECT PROVIDE REVISIONS CONSISTENT WITH | | PREVIOUS FIRE ALARM PERMITTING AND FUNCTION. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|