Plan Review Notes For Permit 17120214 |
Permit Number |
17120214 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-03-20 08:09:15 | 03/19/18 | | HELLO MR. GOMEZ, THIS IS CHRIS WISE WITH LEGACY | | BROTHERS LLC. WE WOULD LIKE TO PROCEED WITH THE PERMIT | | ISSUANCE UNDER PROVISIO, PENDING THE ZONING APPROVAL. I | | SPOKE TO ANGELA AND SHE WILL BE GETTING BACK WITH ME | | TODAY TO FINALIZE. THANK YOU! IF YOU NEED ME FOR | | ANYTHING PLEASE DON?T HESITATE TO REACH OUT. | | CHRIS WISE | | (912)484-0721 | | LEGACY BROTHERS LLC | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE INFO. | | PRIOR TO INSPECTIONS): | | 1- PROVIDE DRAINAGE PLAN. | | 2- REVISE THE ATTIC LIVE LOAD ON SHEET T-1 TO COMPLY | | WITH TABLE R301.5 FBC-RESIDENTIAL. (DROP STAIRS. SEE | | SHEET 1). | | 3- REVISE STRUCTURAL NOTE #3 ON SHEET T-1. ASTM C 1063 | | REQUIRES NAILS THAT PROVIDE MIN. 1-3/4" PENETRATION | | INTO HORIZONTAL FRAMING MEMBERS. STAPLES WITH 7/8" LEGS | | DON'T COMPLY. | | 4- ENERGY CALCULATIONS: (1)NEED FORM R405-2014 NOT | | 2017. (2)BUILDER NAME IS INCORRECT. (3) NEED THE NAME | | OF THE PERSON-PREPARING THEM. | | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) WITH LEGIBLE | | DWGS FOR: (1)ENTRY DOOR THAT MEETS THE DESIGN | | PRESSURES. (2) SINGLE HUNG WINDOWS. (3) SLIDING GLASS | | DOORS. (4)ROOF SHINGLES. (5)PRECAST LINTELS. | | 6- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT | | APPROVALS. | | |
|