Plan Review Notes
Plan Review Notes For Permit 17120214
Permit Number 17120214
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-12 17:14:09NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
 1- REVISE THE GRAVITY LOADS SPECIFIED ON SHEET T-1.
 NEED TO REVISE THE ATTIC LIVE LOAD TO COMPLY WITH TABLE
 R301.5 FBC-RESIDENTIAL.
 RESPONSE: ACCORDING TO PLANS SUBMITTED IT LOOKS LIKE
 THE ATTIC ABOVE GARAGE IS GOING TO BE USED FOR STORAGE.
 SEE SIZE OF ATTIC ACCESS AND OPTIONAL DROP STAIRS.
 REVISE LOADS ACCORDINGLY. SEE TABLE R301.5 FOR REQUIRED
 LIVE LOADS AND REVISE AS REQUIRED. NOTE: REVISE LOADING
 CRITERIA SHOWN ON TRUSS LAYOUT SUBMITTED TO MATCH
 ENGINEER OF RECORD PROPOSED DESIGN CRITERIA.
  
 2- REVISE STRUCTURAL NOTE #3 ON SHEET T-1. ACCORDING TO
 ASTM C 1063 THE HIGH RIB METAL LATH NEED TO BE NAILED
 WITH NAILS OR STAPLES THAT PROVIDE MIN. 1-3/4"
 PENETRATION INTO THE ROOF TRUSS (HORIZONTAL FRAMING
 MEMBERS).
 RESPONSE: NOTE #3 CALLS FOR OPTIONAL STAPLES WITH 7/8"
 LEGS. THIS STAPLES DON'T COMPLY. REVISE AS REQUIRED.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 NEW COMMENT:
 A) FORM R405-2017 SUBMITTED NOW IS INCORRECT. THIS FORM
 IS FOR THE 2017 CODE. THIS BUILDING IS BEING REVIEWED
 UNDER THE 2014 CODE. PROVIDE CORRECT FORM. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) BUILDER NAME IS INCORRECT. IT DOESN'T MATCH BUILDER
 SHOWN ON THE PERMIT APPLICATION. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) PROVIDE THE NAME OF THE PERSON RESPONSIBLE FOR THE
 DESIGN AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 NOTE:
 LABEL REQUIRED FOR DOORS AND WINDOWS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED IN THE ENERGY
 CALCULATIONS IS REQUIRED WHEN THE CALCULATIONS DON'T
 USE THE PROGRAM'S DEFAULT FACTOR.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. NEED
 DOOR THAT MEETS OR EXCEEDS THE CALCULATED DESIGN
 PRESSURES. DRAWING MA-FL0222-17 SUBMITTED DOESN'T MEET
 THEM. NOTE: ALSO, PROVIDE COMPLETE PRODUCT APPROVAL
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWINGS SUBMITTED. OR PROVIDE MIAMI
 DADE NOA. OR MANUFACTURER MAY SUBMIT COMPLETE
 ENGINEERING PACKAGE FOR SITE SPECIFIC INSTALLATION.
 SUBMIT TWO COPIES. ALSO, DRAWINGS ARE NOT LEGIBLE
 BECAUSE THEY ARE TOO SMALL. PRINT DRAWINGS IN LANDSCAPE
 FORMAT SO THEY USE THE WHOLE PAPER AND ARE MORE
 LEGIBLE.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. SUBMIT TWO
 COPIES OF NOA 15-0602.06. ONLY ONE WAS SUBMITTED. ALSO,
 DRAWINGS ARE NOT LEGIBLE BECAUSE THEY ARE TOO SMALL.
 PRINT DRAWINGS IN LANDSCAPE FORMAT SO THEY USE THE
 WHOLE PAPER AND ARE MORE LEGIBLE.
  
 C) SLIDING GLASS DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED. OR PROVIDE MIAMI DADE NOA. OR MANUFACTURER
 MAY SUBMIT COMPLETE ENGINEERING PACKAGE FOR SITE
 SPECIFIC INSTALLATION. SUBMIT TWO COPIES. ALSO,
 DRAWINGS ARE NOT LEGIBLE BECAUSE THEY ARE TOO SMALL.
 PRINT DRAWINGS IN LANDSCAPE FORMAT SO THEY USE THE
 WHOLE PAPER AND ARE MORE LEGIBLE.
  
 D) ROOF SHINGLES AS SHOWN ON PLANS. SUBMIT TWO COPIES
 OF NOA 12-1127.03. ONLY ONE WAS SUBMITTED.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. REPEAT
 COMMENT.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 R401.3 DRAINAGE: SURFACE DRAINAGE SHALL BE DIVERTED TO
 A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 ****PLEASE PROVIDE RESPONSE LETTEER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]