 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 2. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF
 RESISTANCE TO GROUND OF 25 OHMS OR LESS. PROVIDE
 INTERSYSTEM BONDING TERMINATION POINT AT SERVICE (SHOW
 ON RISER DIAGRAM). NEC 250.6, 250.94; FBC RE3609.3
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE3602.3
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR BATH 2. NEC 210.11(C)(3), 210.52(D); FBC
 RE 3703.4, 3901.6
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 7. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC
 RE3902.2
 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. THE
 PANEL SCHEDULE SHOWS A LOAD OF 8000 WATTS, WHICH IS A
 LOAD OF APPROXIMATELY 33.33 AMPS. HOWEVER, THE BREAKER
 IS FOR THIS IS SHOWN AS AN 80 AMP BREAKER. NEED
 CLARIFICATION OF SIZE REQUIRED. NEC 110.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved