2017-12-07 09:06:43FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220 FOR MS-1 AND FOR NEW PANEL AND TRANSFROMER
 FEEDING FCSP-3
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10