2017-12-05 18:26:04 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1-PERMIT APPLICATION DESCRIBES RE-ROOF OF 3 SQUARES OF |
| FLAT ROOF. PROVIDE PRODUCT APPROVAL (2 COPIES) OF FLAT |
| ROOF PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001. |
| NO PRODUCT APPROVAL WAS SUBMITTED AT THIS TIME. CLEARLY |
| SPECIFY ASSEMBLY TO BE INSTALLED. AND PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| NOTE: KEEP IN MIND THAT THIS HOUSE IS LOCATED IN |
| EXPOSURE "D". THIS IS IMPORTANT WHEN DETERMINING THE |
| ROOF DESIGN PRESSURES. |
| |
| 2- MEAN ROOF HEIGHT SPECIFIED ON THE PERMIT APPLICATION |
| IS INCORRECT. THIS HOUSE HAS A SECOND FLOOR. THEREFORE, |
| 12'-0" MEAN ROOF HEIGHT IS INCORRECT. REVISE AS |
| REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 3- ROOF TILE NOA 16-0711.05 SUBMITTED: CLEARLY MARK ON |
| THE NOA THE ROOF TILE FASTENING METHOD TO BE USED TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301.1 FBC-RESIDENTIAL. NOTE: KEEP IN MIND THAT THIS |
| BUILDING IS LOCATED IN EXPOSURE "D". IF USING SCREWS, |
| THEN SPECIFY NUMBER OF SCREWS AND SIZE. IF USING |
| ADHESIVE, THEN PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| REQUIRED BY FAC 61G20-3.001. |
| |