2017-12-05 18:26:04RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1-PERMIT APPLICATION DESCRIBES RE-ROOF OF 3 SQUARES OF
 FLAT ROOF. PROVIDE PRODUCT APPROVAL (2 COPIES) OF FLAT
 ROOF PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001.
 NO PRODUCT APPROVAL WAS SUBMITTED AT THIS TIME. CLEARLY
 SPECIFY ASSEMBLY TO BE INSTALLED. AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 NOTE: KEEP IN MIND THAT THIS HOUSE IS LOCATED IN
 EXPOSURE "D". THIS IS IMPORTANT WHEN DETERMINING THE
 ROOF DESIGN PRESSURES.
  
 2- MEAN ROOF HEIGHT SPECIFIED ON THE PERMIT APPLICATION
 IS INCORRECT. THIS HOUSE HAS A SECOND FLOOR. THEREFORE,
 12'-0" MEAN ROOF HEIGHT IS INCORRECT. REVISE AS
 REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- ROOF TILE NOA 16-0711.05 SUBMITTED: CLEARLY MARK ON
 THE NOA THE ROOF TILE FASTENING METHOD TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: KEEP IN MIND THAT THIS
 BUILDING IS LOCATED IN EXPOSURE "D". IF USING SCREWS,
 THEN SPECIFY NUMBER OF SCREWS AND SIZE. IF USING
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY FAC 61G20-3.001.
  