2017-12-21 14:16:55 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. CS.1 UNDER THE PLUMBING FIXTURE REQUIREMENTS |
| THE FBC PL 403.1.1 REQUIRES THAT THE OCCUPANT LOAD BE |
| DIVIDED BETWEEN MEN AND WOMEN THEN APPLIED TO TABLE |
| 403.1 . PER FLOOR THE CODE REQUIRES 3WC FOR MEN AND 3WC |
| FOR WOMEN, 3 LAVATORY'S FOR MEN AND 3 LAVATORY'S FOR |
| WOMEN WHICH YOU HAVE PROVIDED OVER FOR CLARITY PLEASE |
| CORRECT THE CALCULATIONS ON SHT. CS.1 |
| |
| 2. PLEASE SHOW THE HEIGHT OF THE GRAB BARS IN THE |
| SHOWER. SHALL COMPLY WITH FBC ACC 608.3.1 AND 609.4 |
| |
| 3. PLEASE SHOW COMPLIANCE OF THE SHOWER SEAT PER FBC |
| ACC 610.3 AND 610.3.1 |
| |
| 4. URINALS SHALL NOT BE SET CLOSER THAN 15 INCHES FROM |
| ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR |
| OTHERE OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER TO |
| CENTER BETWEEN ADJACENT FIXTURES. THE DIMENSION OF 24" |
| ON SHT A4.2 WILL NOT COMPLY. PER FBC PL 405.3.1 |
| |
| 5. SHT. A4.3 SHOW DIMENSIONS OF GRAB BARS IN AMBULATORY |
| STALLS. FBC ACC 609.4 |
| |
| 6. SHT. A4.2 SHOW THE DIMENSION 7"-9" FOR THE CENTER OF |
| THE TOILET PAPER DISPERSER OFF THE FRONT OF THE TOILET. |
| FBC ACC 604.7 |
| |
| 7. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. DRY |
| WALL WITH WASHABLE PAINT DOES NOT COMPLY. PER FBC |
| 1210.2.2 |
| |
| 8. SHT. P2.1AND P5.1 SHOWS A HORIZONTAL DRY VENT ON THE |
| MOP SINK FOR THE FIRCT FLOOR WHICH DOES NOT COMPLY WITH |
| CODE PLEASE REMOVE FROM PLAN THAT MOP SINK WILL BE |
| VENTED BY THE DRINKING FOUNTAIN STACK. PER FBC PL 905.3 |
| AND 905.4 |
| |
| 9. SHT. P5.1 THE DRAIN FROM ELEVATOR SUMP PUMP SHALL BE |
| INDIRECT WASTE AS SHOWN ON DETAIN SHT. P0.1. PER FBC PL |
| 802.1.5 |
| |
| 10. P5.1 SHOWS EACH BANK OF FIXTURES ON EACH FLOOR |
| VENTING THROUGH THE ROOF SEPARATELY IS THIS CORRECT 7 |
| SEPARATE ROOF PENETRATIONS PLEASE CLARIFY PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 11. SHT. P0.1 ON THE WATER HEATER DETAIL THE NOTE AT |
| THE BOTTOM IS INCORRECT THE FBC ENERGY CODE SEC SHOULD |
| BR C404.3 AND A MIXING VALVE ON THE LAVATORY'S DOES NOT |
| COMPLY WITH FBC PL 604.3 TEMPERED WATER SHALL BE |
| DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| B125.3. IF THESE LAVATORY'S ON THIS PROJECT ARE NOT |
| PUBLIC THEY DO NOT HAVE TO COMPLY. |
| |
| 12. SHT. P5.1 THE HANDICAP WC IN THE MENS BATHROOM ON |
| THE FIRST FLOOR SHALL BE VENTED BY THE LAVATORY |
| CONNECTED TO THE WC FIXTURE BRANCH DRAIN. PER FBC PL |
| 912.1 |
| |
| 13. ARE THER ANY STORM DRAIN ON THIS BUILDING OR ARE |
| THEY EXISTING PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |