2017-12-21 14:16:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. CS.1 UNDER THE PLUMBING FIXTURE REQUIREMENTS
 THE FBC PL 403.1.1 REQUIRES THAT THE OCCUPANT LOAD BE
 DIVIDED BETWEEN MEN AND WOMEN THEN APPLIED TO TABLE
 403.1 . PER FLOOR THE CODE REQUIRES 3WC FOR MEN AND 3WC
 FOR WOMEN, 3 LAVATORY'S FOR MEN AND 3 LAVATORY'S FOR
 WOMEN WHICH YOU HAVE PROVIDED OVER FOR CLARITY PLEASE
 CORRECT THE CALCULATIONS ON SHT. CS.1
  
 2. PLEASE SHOW THE HEIGHT OF THE GRAB BARS IN THE
 SHOWER. SHALL COMPLY WITH FBC ACC 608.3.1 AND 609.4
  
 3. PLEASE SHOW COMPLIANCE OF THE SHOWER SEAT PER FBC
 ACC 610.3 AND 610.3.1
  
 4. URINALS SHALL NOT BE SET CLOSER THAN 15 INCHES FROM
 ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR
 OTHERE OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER TO
 CENTER BETWEEN ADJACENT FIXTURES. THE DIMENSION OF 24"
 ON SHT A4.2 WILL NOT COMPLY. PER FBC PL 405.3.1
  
 5. SHT. A4.3 SHOW DIMENSIONS OF GRAB BARS IN AMBULATORY
 STALLS. FBC ACC 609.4
  
 6. SHT. A4.2 SHOW THE DIMENSION 7"-9" FOR THE CENTER OF
 THE TOILET PAPER DISPERSER OFF THE FRONT OF THE TOILET.
 FBC ACC 604.7
  
 7. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. DRY
 WALL WITH WASHABLE PAINT DOES NOT COMPLY. PER FBC
 1210.2.2
  
 8. SHT. P2.1AND P5.1 SHOWS A HORIZONTAL DRY VENT ON THE
 MOP SINK FOR THE FIRCT FLOOR WHICH DOES NOT COMPLY WITH
 CODE PLEASE REMOVE FROM PLAN THAT MOP SINK WILL BE
 VENTED BY THE DRINKING FOUNTAIN STACK. PER FBC PL 905.3
 AND 905.4
  
 9. SHT. P5.1 THE DRAIN FROM ELEVATOR SUMP PUMP SHALL BE
 INDIRECT WASTE AS SHOWN ON DETAIN SHT. P0.1. PER FBC PL
 802.1.5
  
 10. P5.1 SHOWS EACH BANK OF FIXTURES ON EACH FLOOR
 VENTING THROUGH THE ROOF SEPARATELY IS THIS CORRECT 7
 SEPARATE ROOF PENETRATIONS PLEASE CLARIFY PER WPB AMEND
 TO FBC 107.2.1
  
 11. SHT. P0.1 ON THE WATER HEATER DETAIL THE NOTE AT
 THE BOTTOM IS INCORRECT THE FBC ENERGY CODE SEC SHOULD
 BR C404.3 AND A MIXING VALVE ON THE LAVATORY'S DOES NOT
 COMPLY WITH FBC PL 604.3 TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. IF THESE LAVATORY'S ON THIS PROJECT ARE NOT
 PUBLIC THEY DO NOT HAVE TO COMPLY.
  
 12. SHT. P5.1 THE HANDICAP WC IN THE MENS BATHROOM ON
 THE FIRST FLOOR SHALL BE VENTED BY THE LAVATORY
 CONNECTED TO THE WC FIXTURE BRANCH DRAIN. PER FBC PL
 912.1
  
 13. ARE THER ANY STORM DRAIN ON THIS BUILDING OR ARE
 THEY EXISTING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711