Plan Review Notes
Plan Review Notes For Permit 17120042
Permit Number 17120042
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-21 12:25:301ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES.
 PERMIT #17120042
 12/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M6.3 & M7.3 WERE NOT SUBMITTED WITH THE PLAN
 SETS, AND THERE ARE TWO DIFFERENT M6.1 SHEETS. DUE TO
 THESE PLAN OMISSIONS, THE AC EQUIPMENT SCHEDULES FOR
 SYSTEMS IN THE OCCUPIED AREAS ARE NOT AVAILABLE TO
 REVIEW AND COMPARE WITH THE CALCULATIONS.
  
 2) THE ENERGYGAUGE COMPLIANCE REPORT IS LISTING DATA
 FOR ZONES AND AHU IDENTIFICATIONS THAT DO NOT MATCH
 WITH THE PLANS- THERE ARE NO ZONES SHOWN ON THE PLANS,
 AND THE AHU'S SHOWN ON THE PLANS ARE LABELED 1-1, 1-2,
 2-1, 2-2, 3-1, 3-2, AND 4-1.
  
 3) THE AC CALCULATIONS ARE INDICATING THAT THE SYSTEMS
 SELECTED (AS SHOWN ON THE ENERGY CALCULATIONS ) ARE
 OVERSIZED- SEE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 4) THE ENERGY REPORT IS MISSING COMPLIANCE DATA FOR THE
 CHILLER, THE 3-TON MINI SPLIT SYSTEM, AND THE PIPING
 SYSTEM.
  
 5) M7.2: THE SYSTEM RISER DIAGRAM SHOWS TWO CHILLERS,
 TWO ERV'S, AND WFC SYSTEMS THAT ARE NOT SHOWN ON THE
 PLANS - PLEASE CLARIFY.
  
 6) M2.1, M2.2, M2.3: THE JUMP DUCTS TRANSFERRING AIR
 INTO THE CORRIDORS ARE NOT PERMITTED PER SECTION 601.2.
  
 7) M2.1, M2.2, M2.3: SHOW COMPLIANCE WITH SECTION
 606.2.2 FOR THE AHU'S AND VAV BOXES SHARING THE COMMON
 RETURN PLENUMS ON EACH FLOOR. INDICATE IF AREA SMOKE
 DETECTORS WILL BE INSTALLED IN THE COMMON PLENUM AND
 THE SEQUENCE OF OPERATION FOR SHUTDOWN OF THE AHU'S AND
 VAV BOXES.
  
 8) M2.1 & M2.2: SHOW COMPLIANCE WITH SECTION 401.4 AND
 401.5 RELATING TO THE O/A INTAKES. SUBMIT A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE LOUVERS.
  
 9) PROVIDE A SUBMITTAL FOR THE FIRE DAMPER, AND AN
 INSTALLATION DETAIL ON THE PLAN.
  
 10) PROVIDE A UL LISTED AND LABELED FIRESTOPPING SYSTEM
 FOR THE REFRIGERANT PIPING PENETRATIONS.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE CHILLER AND ROOF FAN INCLUDING ATTACHMENT DETAILS
 AND WIND DESIGN CRITERIA- SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  