2017-12-05 07:33:42 | W. P. B. REVISION: 17111173 / INTERIOR FRAMING SHOP |
| DRAWING FOR TUB DECKS |
| W. P. B. PERMIT: 15111020 |
| ADD: 1100 S. FLAGLER DR. |
| CONT: SUFFOLK |
| TEL: 561-282-3724 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| SUBJECT TO FAIR HOUSING! |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 05/ 2017 |
| ACTION: DENIED |
| |
| 1) 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| RECORD FOR REVIEW. THE STRUCTURAL ENGINEER RALPH |
| CALISTRO HAS NOT REVIEWED THE STRUCTURAL CALCULATIONS |
| NOR PLANS. |
| |
| 2) THE SHOP DRAWINGS HAVE A COPY OF THE ENGINEER?S |
| SIGNATURE, NOT A TRUE BLUE INK SIGNATURE, WHEN HAND |
| WRITTEN YOU DO NOT SEE PIXELS AND THE PAPER IS |
| INDENTED. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715/ FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |