2018-03-23 13:38:37 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| 2015 5TH EDITION |
| |
| SECOND REVIEW FOUNDATION FOR THE CRYSTAL 17111142 |
| |
| DATE: MARRCH 23,2018 |
| |
| PLAN REVIEW RESPONSES ARE ON TO IN CAPS. |
| |
| 1. OK ADDRESSED |
| |
| 2. OK RECIEVED FLOOD ZONE SITE SPEPCIFIC FLOD ZONE |
| ANALYSIS AND ELEVATION CERTIFICATE. |
| |
| FLOOD ZONE CERTIFICATES |
| |
| 3. PARTIALLY ADDRESSED. |
| |
| SUBMIT ONLY THE DOCUMENTS REQUIRED FOR A FOUNDATION |
| PERMIT. THE ENTIRE SET OF PLANS FOR THE MAIN BUILDING |
| HAS BEEN SUBMITTED. |
| SEE LIST ADDED BELOW. THIS IS A TYPICAL LIST OF |
| REQUIRED ITEMS FOR A FOUNDATION PERMIT FOR YOUR |
| REFERENCE. |
| PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION |
| PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) |
| GEOTECHNICAL REPORT |
| SURVEY DRAWING |
| STORM WATER POLLUTION PREVENTION PLAN |
| SITE PLAN |
| 1ST FLOOR ARCHITECTURAL PLAN |
| ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING |
| FOUNDATION PLAN |
| FOUNDATION DETAILS AND CROSS SECTIONS |
| STRUCTURAL ENGINEER'S GENERAL NOTES |
| UNDERGROUND PLUMBING PLAN (IF APPLICABLE) |
| ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF |
| APPLICABLE) |
| ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR |
| EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT). |
| IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT, |
| AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR |
| PLAN SHOWING UNDERGROUND FIRE LINE |
| THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN |
| (AS APPLICABLE) |
| SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) |
| THRESHOLD STATEMENT ON PLAN (IF APPLICABLE) |
| THREE SETS OF PLANS FOR RESIDENT INSPECTOR OR THRESHOLD |
| PROJECT |
| |
| PROVIDE ONLY THE INFORMATION REQUIRED FOR A FOUNDATION |
| PLAN REVIEW. THE ENTIRE BUILDING PACKAGE WAS SUBMITTED. |
| INCLUDE THE ABOVE INFORMATION AS WELL AS ALL STRUCTURAL |
| DETAILS AND ELEVATIONS ALONG WITH THE ELECTRICAL AND |
| PLUMBING PAGES AS NEEDED. |
| |
| FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| |
| 4. OK ADDRESSED. |
| THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| THRESHOLD BUILDING MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION THAT EXCEEDS |
| 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF |
| GREATER THAN 500 PERSONS. |
| |
| 4A. OK ADDRESSED |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 4B. OK ADDRESSED |
| THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. |
| |
| 4C. OK ADDRESSED |
| FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| 5. OK ADDRESSED |
| PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. FBC |
| 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL SHALL |
| NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO UNITS |
| HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR PERMANENT |
| EXCAVATIONS SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL |
| IN TWO UNITS HORIZONTAL (50-PERCENT SLOPE). DEVIATION |
| FROM THE FOREGOING LIMITATIONS FOR CUT SLOPES SHALL BE |
| PERMITTED ONLY UPON THE PRESENTATION OF A SOIL |
| INVESTIGATION REPORT ACCEPTABLE TO THE BUILDING |
| OFFICIAL. |
| |
| 6. OK ADDRESSED |
| WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON |
| SITE? FBC 3304.1.2 SURCHARGE. NO FILL OR OTHER |
| SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY |
| BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE |
| IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED |
| BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR |
| FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION |
| SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED |
| AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER |
| MOVEMENT. |
| |
| 7. OK ADDRESSED |
| PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION |
| PLAN. FBC 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC |
| AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE |
| DURING CONSTRUCTION, REMODELING AND DEMOLITION WORK. |
| PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF AND |
| EROSION DURING CONSTRUCTION OR DEMOLITION ACTIVITIES. |
| THE PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE |
| SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| OF THE EXCAVATION. |
| FBC 109.3.10 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 8. OK ADDRESSED |
| FBC 3306.9 ADJACENT TO EXCAVATIONS. EVERY EXCAVATION ON |
| A SITE LOCATED 5 FEET (1524 MM) OR LESS FROM THE STREET |
| LOT LINE SHALL BE ENCLOSED WITH A BARRIER NOT LESS THAN |
| 6 FEET (1829 MM) HIGH. WHERE LOCATED MORE THAN 5 FEET |
| (1524 MM) FROM THE STREET LOT LINE, A BARRIER SHALL BE |
| ERECTED WHEN REQUIRED BY THE BUILDING OFFICIAL. |
| BARRIERS SHALL BE OF ADEQUATE STRENGTH TO RESIST WIND |
| PRESSURE AS SPECIFIED IN CHAPTER 16. |
| |
| 9. OK ADDRESSED TRAILER PERMIT IN APPLICATION |
| ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR BUILDINGS) |
| THAT ARE GOING TO HAVE MEETING IN THEM WILL BE REQUIRED |
| TO GET A PERMIT, 102.2(E) MOBILE OR MODULAR STRUCTURES |
| USED AS TEMPORARY OFFICES, EXCEPT THAT THE PROVISIONS |
| OF PART V FS 553.501-553.513, FLORIDA STATUTES, |
| RELATING TO ACCESSIBILITY BY PERSONS WITH DISABILITIES, |
| AND PERMITS SHALL BE REQUIRED FOR STRUCTURAL SUPPORT |
| AND TIE DOWN, ELECTRICAL SUPPLY, AND ALL UTILITY |
| CONNECTIONS TO SUCH MOBILE OR MODULAR STRUCTURES. |
| |
| 10. OK ADDRESSED RECEIVED SOILS REPORT. |
| PROVIDE SOILS EXPLORATION REPORT THAT WAS COMPLETED BY |
| NUTTING ENGINEERING. |
| GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN |
| ACCORDANCE WITH FBC SECTION 1803.2 AND REPORTED IN |
| ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE |
| BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS |
| INVOLVE IN-SITU TESTING, LABORATORY TESTING OR |
| ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE |
| CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL. |
| |
| FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| 11. NOT ADDRESSED. SEE IMPACT FEE STOP ADDED. |
| BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| INFORMATION. |
| |
| 12. OK ADDRESSED |
| FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF |
| THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| AT THE HOLDERS OWN RISK WITH THE BUILDING OPERATION AND |
| WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |