Date |
Text |
2017-12-20 08:35:08 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: TO EXPEDITE APPROVAL OF THIS PERMIT |
| I SUGGEST SCHEDULING A MEETING TO GO OVER COMMENTS SEE |
| MY CONTACT INFO BELOW. |
| |
| 1. THIS BUILDING SHALL COMPLY WITH FHA. PER FAIR |
| HOUSING ACCESSIBILITY GUIDELINES : SECTION 3. FAIR |
| HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS |
| |
| THE REGULATIONS ISSUED BY THE DEPARTMENT AT 24 CFR |
| 100/205 STATE: |
| |
| SECTION 100.205 DESIGN AND CONSTRUCTION REQUIREMENTS. |
| (A) COVERED MULTIFAMILY DWELLINGS FOR FIRST OCCUPANCY |
| AFTER MARCH 13, 1991, SHALL BE DESIGNED AND CONSTRUCTED |
| TO HAVE AT LEAST ONE BUILDING ENTRANCE ON AN ACCESSIBLE |
| ROUTE UNLESS IT IS IMPRACTICAL TO DO SO BECAUSE OF THE |
| SITE. FOR PURPOSES OF THIS SECTION, A COVERED |
| MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND |
| CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, |
| 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST |
| BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED |
| MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR |
| LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990. THE |
| BURDEN OF ESTABLISHING IMPRACTICALITY BECAUSE OF |
| TERRAIN OR UNUSUAL SITE CHARACTERISTICS IS ON THE |
| PERSON OR PERSONS WHO DESIGNED OR CONSTRUCTED THE |
| HOUSING FACILITY. |
| |
| A) INDICATE ON THE PLAN WHICH FHA DESIGN DOCUMENT WILL |
| BE USED IN DESIGNING BUILDING TO MEET FHA REQUIREMENTS. |
| PER WPB AMEND TO FBC 107.2.1 |
| B) INDICATE ON THE PLAN HOW FHA REQUIREMENTS 1-5 WILL |
| BE MET. |
| C) SHOW ON THE PLANS THE DIMENSIONS OF THE MOUNTING |
| HEIGHTS FOR THE GRAB BAR BACKING. PER FHA REQUIREMENT 6 |
| D) INDICATE ON THE PLAN WHICH DESIGN SPEC WILL BE USED |
| FOR THE BATHROOMS. PER FHA REQUIREMENT 7 |
| E) SHOW ON THE PLAN THE CLEAR FLOOR SPACE REQUIRED AT |
| THE FIXTURES IN THE BATHROOMS AND KITCHEN. PER FHA |
| REQUIREMENT 7 |
| F) SHOW ON THE PLANS THE DIMENSIONS FOR THE HEIGHT AND |
| DEPTH OF THE VANITY OR WING WALL ADJACENT TO THE WATER |
| CLOSET. PER FHA REQUIREMENT 7 |
| |
| 2. PLEASE INDICATE ON THE PLAN FOR FOUNDATION ONLY. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHT. A701 SHOW THE SQFT AT EACH ROOF DRAIN. PER WPB |
| AMEND TO FBC 107.2.1 AND FBC PL CH 11 |
| |
| 4. ON SHT. P-1 AND P-5 IT SHOWS 685 SQFT ON 3 OF THE |
| ROOF DRAINS ON SHT A701 IT SHOWS THOSE SAME ROOF AREAS |
| AS 3 DIFFERENT SIZES PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 5. SHT. P-1 PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT |
| IS REQUIRED FOR BACKFLOW DEVICES. PER WPB UTILITIES |
| DEPARTMENT |
| |
| 6. SHT. P-6 SHOW SIZE ON THE BRANCH'S ON WATER MAIN |
| RISER. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7.SHT. P-1 SHOWS THE HOT AND COLD WATER PIPING TO THE |
| WATER HEATER ON THE GROUND FLOOR AS 1/2" THE ISOMETRIC |
| SHOWS IT AT 3/4" PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 8. PLEASE LABEL ALL ALL WASTE AND SOIL STACKS ON |
| ISOMETRICS , RISERS AND FLOOR PLANS. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 9. SHT. P-7 SHOW BRANCH'S AND SIZE OF BRANCH ON THE |
| RISERS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 10. SHT. P-8 SHOWS 2 ROUND ROOF DRAINS FOR OBSERVATION |
| DECK SHT. A701 SHOWS 3 LINEAR FLOOR DRAINS ON THE |
| OBSERVATION DECK PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 11. LABEL STORM RISER TO MATCH THE FLOOR PLAN. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 12. PLEASE SHOW PUMP AND DRAIN PIPING FOR ELEVATOR |
| SUMP. PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |