Plan Review Notes For Permit 17111142 |
Permit Number |
17111142 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-07 09:52:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO CIVIL DRAWINGS OR ANY OTHER DRAWING | | INDICATING THE LOCATION OF A FDC, FIRE HYDRANT OR | | PROPOSED UNDERGROUND FIRE LINE. | | | | ADDITIONALLY, PROVIDE A NOTE INDICATING THAT ALL FIRE | | LINE SHALL BE UNDER SEPARATE SHOP DRAWINGS IN | | COMPLINACE WITH NFPA 24, STANDARD FOR THE INSTALLATION | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, | | 2010 EDITION. | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | 2) THE ARE NO INDICATIONS OF GRADE SLOPES ON THE ACCESS | | ROAD AND/OR THE PREVIOUSLY DISCUSSED LOCATION OF FIRE | | APPARATUS AT THE WEST END OF THE BUILDING. IT WAS | | DISCUSSED THAT THAT AREA WOULD BE FLAT AND HAVE THE FDC | | AND FIRE HYDRANT LOCATED THERE.(SEE # 1) | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|