2017-12-07 09:52:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO CIVIL DRAWINGS OR ANY OTHER DRAWING
 INDICATING THE LOCATION OF A FDC, FIRE HYDRANT OR
 PROPOSED UNDERGROUND FIRE LINE.
  
 ADDITIONALLY, PROVIDE A NOTE INDICATING THAT ALL FIRE
 LINE SHALL BE UNDER SEPARATE SHOP DRAWINGS IN
 COMPLINACE WITH NFPA 24, STANDARD FOR THE INSTALLATION
 OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES,
 2010 EDITION.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) THE ARE NO INDICATIONS OF GRADE SLOPES ON THE ACCESS
 ROAD AND/OR THE PREVIOUSLY DISCUSSED LOCATION OF FIRE
 APPARATUS AT THE WEST END OF THE BUILDING. IT WAS
 DISCUSSED THAT THAT AREA WOULD BE FLAT AND HAVE THE FDC
 AND FIRE HYDRANT LOCATED THERE.(SEE # 1)
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  