Plan Review Notes
Plan Review Notes For Permit 17111142
Permit Number 17111142
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-14 14:07:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS
 BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY.
 THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN
 PERMIT.
  
 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED
 FOR FIRE PUMP. NEC 695.3(B)
 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN
 THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6,
 695.4(B)(2), 230.79
 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED
 EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE
 LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE
 CORRECTION. NEC 695.4(B)(3), 230.72(B)
 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED
 ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS
 OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3,
 695.10
 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE
 PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC
 WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE
 CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE
 ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1
 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC
 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL
 HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE
 CLARIFICATION AND CORRECTIONS. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  