2017-12-14 14:07:35 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS |
| BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY. |
| THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN |
| PERMIT. |
| |
| 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED |
| FOR FIRE PUMP. NEC 695.3(B) |
| 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN |
| THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6, |
| 695.4(B)(2), 230.79 |
| 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED |
| EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE |
| LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE |
| CORRECTION. NEC 695.4(B)(3), 230.72(B) |
| 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED |
| ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS |
| OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3, |
| 695.10 |
| 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE |
| PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC |
| WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE |
| CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE |
| ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1 |
| 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE |
| SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC |
| 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL |
| HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE |
| CLARIFICATION AND CORRECTIONS. NEC 220 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |