2017-12-28 12:21:25NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION.
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE DOOR
 LEADING TO THE MAIN HOUSE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL.
  
 4- DESIGN LOADS SPECIFIED UNDER GENERAL CONSTRUCTION
 NOTES ON SHEET A-1 DON'T MATCH DESIGN LOADS SPECIFIED
 ON THE ROOF FRAMING NOTES AND TRUSS DESIGN CRITERIA ON
 SHEET S-3. REVISE AS REQUIRED TO MATCH. NOTE: ALL THE
 DESIGN LOADS SPECIFIED ON THE 3 PLACES NEED TO MATCH
 ALSO. INCLUDE THE STORAGE LOADS AT THE GARAGE ATTIC.
 SEC. R301.1 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
  
 5- SPECIFY ON PLANS CARBON MONOXIDE ALARMS BY ALL
 BEDROOMS IN THE LOCATIONS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 6- FLOOR PLAN ON SHEET A-1 CALLS FOR BEDROOM #4 ON THE
 TOP LEFT CORNER OF THE DRAWING. CLARIFY WHERE IS
 BEDROOM #3?. SEC. 107.2.1 CITY AMENDMENTS. NOTE: NUMBER
 OF BEDROOMS NEEDS TO BE CORRECT SO ENERGY CALCULATIONS
 ARE DONE CORRECTLY ALSO.
  
 7- SIZE OF FOOTING SPECIFIED ON FOUNDATION PLANS ON
 SHEET S-1 DOESN'T MATCH SIZE SHOWN ON WALL SECTION
 1/S-4. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- WINDOW NOTE # 3 ON SHEET S-2: CLARIFY WHERE ARE THE
 SHIM SPECIFICATIONS TAKEN FROM?. SEE PRODUCT APPROVALS
 FOR LIMITATION ON SHIM. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- ENERGY CALCULATIONS SUBMITTED:
 A) NUMBER OF BEDROOMS DON'T MATCH PLANS. NOTE:
 COORDINATE WITH ENGINEER OF RECORD AND REVISE AS
 REQUIRED. COORDINATE WITH ITEM #6 ABOVE. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) PAGE 2 OF 4 SPECIFIES AN ATTIC VENTILATION RATIO OF
 1/300. PLANS DON'T PROVIDE ANY SPECIFICATIONS FOR THE
 1/300 VENT RATIO. TYPICALLY THE VENT RATIO IS 1/150. IF
 USING THE 1/300 VENT RATIO, THEN PLANS WILL NEED TO BE
 REVISED SHOWING COMPLIANCE WITH THIS RATIO AS REQUIRED
 BY THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL.
 COORDINATE WITH ENGINEER OF RECORD AND REVISE AS
 REQUIRED.
  
 D) WALLS AND WINDOWS ORIENTATION NEED TO BE REVISED TO
 MATCH PLANS. NOTE: SEE SURVEY AND SITE PLAN FOR THE
 CORRECT ORIENTATION. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) COOLING AND HEATING INFORMATION DOESN'T MATCH
 EQUIPMENT SIZING CALCULATIONS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
  
 NOTE:
 LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WHEN
 THE CALCULATIONS DON'T USE THE PROGRAM'S DEFAULT
 FACTOR.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE PRECAST LINTELS AS SPECIFIED ON
 PLANS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  