2017-12-15 15:45:4112/15/2017 1ST GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
 PER CITY RECORDS THERE IS EXISTING GAS EQUIPMENT THAT
 YOU HAVE NOT INCLUDED. THE TOTAL EXISTING SYSTEM IS
 SHOWING @ 573,000BTU AND PER FPU THE MAX THAT METER IS
 ABLE TO FLOW @ .5LB. YOU WILL NEED TO ADDRESS THE
 FOLLOWING
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF ALL EXISTING PIPE PER
 2014 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014
 FBC-RES SEC. G2413
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. THERE IS A POOL HEATER AND
 OUTSIDE BBQ YOU HAVE NOT INCLUDED. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413
  
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 4) THE EXISTING GAS SYSTEM WAS DESIGNED WITH A 0.5 IN.
 W.C PRESSURE DROP SO YOU MUST DESIGN YOU GAS LINE TO
 MATCH. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
  
 5) THE PLANS INDICATE AN EXISTING GAS METER AND WILL BE
 UNDERSIZED BY ADDED ADDITIONAL LOAD. THE BTU LOAD OF
 THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC
 SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 IF YOU ARE UPGRADING THE CURRENT SYSTEM TO A 2LB SYSTEM
 YOU WILL ALSO NEED THE FOLLOWING
  
 1) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  
 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER