2017-12-18 06:52:00 | 1) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THE | | INSTALLATION OF A GAS POOL HEATER. THE BTU LOAD OF THE | | EXISTING POOL HEATER SHALL BE ADDED TO THE TOTAL BTU | | LOAD OF THE SYSTEM AND THE POOL HEATER SHALL BE SHOWN | | ON THE GAS RISER DIAGRAM WITH ALL EXISTING PIPE SIZES. | | FBC-FUEL GAS SEC. 401.4. | | 2) THE DESCRIPTION OF WORK ON THE GAS PERMIT | | APPLICATION REFERS TO CONNECTION TO AN EXISTING NATURAL | | GAS METER YET THE GAS RISER NOTES A NEW 2 LB. METER. | | REVISE THE DESCRIPTION OF WORK TO SHOW A NEW GAS | | METER.WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | PRESSURE REGULATOR FOR THE GENERATOR. THE REGULATOR | | SHALL COMPLY WITH FBC-FUEL GAS SEC.410.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|