Plan Review Notes
Plan Review Notes For Permit 17110988
Permit Number 17110988
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-11 17:03:54FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE DISCONNECT SWITCH AT SIGN LOCATION. NEC 600.6
  
 PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC CE 405.2.4
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A
 SIGN OR OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED
 BY AN EXTERNALLY OPERABLE SWITCH
 OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS WITHIN SIGHT OF THE SIGN
 NEC 600.6(A)(1)
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO
 TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS
 SHALL BE PHOTOSENSOR & TIME CLOCK
 OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.4
  
  