Plan Review Notes For Permit 17110900 |
Permit Number |
17110900 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-22 16:49:41 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- EQUIPMENT SIZING WAS CHANGED. PROVIDE COMPLETE | | EQUIPMENT SIZING CALCULATIONS. SEC. M1401.3 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | 2- A/C PLAN: PROVIDE THE NAME AND SIGNATURE OF THE A/C | | CONTRACTOR RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|