2017-12-19 14:39:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110858
 12/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE CORRIDOR SHALL NOT BE USED TO RETURN
 AIR TO THE MECHANICAL ROOM- SECTION 601.2.
  
 2) M2.1: SHOW THE RETURN AIR OPENING INTO THE
 MECHANICAL ROOM, AND SHOW THE REQUIRED SMOKE
 DETECTOR(S) IN THE ROOM PER SECTION 606.2.2.
  
 3) M2.1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED TO THE
 ROOMS AND SPACES AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS- SECTION 403.
  
 4) M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 5) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HEAT PUMP- C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  