Plan Review Notes
Plan Review Notes For Permit 17110857
Permit Number 17110857
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-18 13:28:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED,
 FIRST FLOOR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE RATIO
 AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT SHALL BE
 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1
  
 2. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED,
 SECOND FLOORR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE
 RATIO AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT
 SHALL BE 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE
 403.1
  
 3. SHT. LS .1.1 WHAT WILL THE ROOF TERRACE BE USED FOR
 IF IT IS USED FOR THE RESTAURANT PATRONS FOR DINNING IT
 SHALL BE CONSIDERED AN A-2 WITH A FIXTURE RATIO OF 1
 PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1
  
 4. SHT LS .1.1 FOR THE A-2 RESTAURANT OCCUPANCY A WATER
 FOUNTAIN IS NOT REQUIRED BUT FOR THE BUSINESS OR
 MERCANTILE OCCUPANCY'S WITH A OCCUPANT LOAD OVER 15 A
 WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE 403.1
  
 5. PLEASE PROVIDE FIXTURE COUNT FOR THE OCCUPANTS OF
 THE PARK NEXT TO RESTAURANT AND THE STANDARD THAT IT
 WAS DESIGNED UNDER. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT LS .1.2 SYSTEM NO-C-AJ-1014 PART OF THE TEXT IS
 CUT OFF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. PROVIDE DETAIL WITH A SYSTEM DESIGNED FOR PLASTIC
 PIPE LARGE THAN 2". PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. A2-2-2 DETAIL PLEASE SHOW CLEAR FLOOR SPACE FOR
 WATER CLOSETS. PER FBC ACC 604.3.1
  
 9. SHT. A2-2-2 LABEL ALL CLEAR FLOR SPACES WITH
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
  
 10.SHT. A2-2-2 THE GRAB BARS SHALL BE MEASURE FROM THE
 GRIPPING SURFACE TI FINISHED FLOOR. PER FBC ACC 609.4
  
 11. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 12. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 13. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 14. SHT. A8-2-1 DETAIL #3 PLEASE SHOW PLEASE SHOW HOW
 THE-ROOF DRAIN WILL BE SECURED TO STRUCTURAL SLAB. PER
 WPB AMEND TO FBC 107.2.1
  
 15. SHT. P2.1.1 PROVIDE NOTE ON PLAN OR SHOW ON RISER
 COMPLIANCE WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THEOUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 16. HOW WILL THE FUTURE CAPPED SANITARY LINE BE
 LOCATED-UNDER THE SLAB. PER WPB AMEND TO FBC 107.2.1
  
 17. SHT. P3.2.1 PLEASE SHOW DFU LOAD ON SANITARY
 ISOMETRIC. PER FBC PL 710.1 AND TABLE 710.1(1)
  
 18. SHT. P3.3.1 THE PIPE SIZE IS MISSING PLEASE CLARIFY
 PER WPB AMEND TO FBC 107.2.1
 A) THE BRANCH FROM SECOND FLOOR TROUGH DRAIN
 B) THE BRANCH FROM THR RISER CONNECTING TROUGH DRAINS
  
 19. P3.3.1 SQFT IS MISSING ON BRANCH CONNECTING THE
 ROOF TERRACE TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1
  
 20. PROVIDE SIZING CALCULATIONS FROM SCHEIR
 MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
  
 21. SHT. P3.3.1 THE 4" BRANCH CONNECTING THR TRENCH
 DRAIN-AND A + B STACKS FROM THE ROOF TERRACE IS
 UNDERSIZED PER FBC PL TABLE 1106.3
  
 22. SHT. P3.3.1 SHOW SQFT ON OVERFLOW PIPING. PER WPB
 AMEND TO FBC 107.2.1
  
 23. SHT. P3.3.1 THE 6" HORIZONTAL OVERFLOW DRAIN PIPE
 IS UNDERSIZED PER FBC PL TABLE 1106.3
  
 24. SHT. P3.3.1 THE SECOND SECTION OF 8" HORIZONTAL
 DRAIN PIPE WITH 12796 SQFT IS UNDERSIZED PER FBC PL
 TABLE 1106.3
  
 25. SHT. P3.3.1 WHAT LEVEL IS THE TRENCH DRAIN THAT IS
 LABELED WITH 350 SQFT PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 26. SHT. P4.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED
 AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR
 A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT.
 SEE STANDARD DETAIL GS 7 OR GS 7.1
  
 27. P4.1.1 MIAMI DADE CODES DO NOT APPLY TO THIS
 PROJECT PLEASE REMOVE ANY REFERENCES FROM PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 28. P4.2.1 DETAIL WITH SPACING OF PIPE HANGERS DOES NOT
 COMPLY WITH FBC PL TABLE 308.5 PLEASE CLARIFY
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  