Date |
Text |
2017-12-18 13:28:51 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, |
| FIRST FLOOR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE RATIO |
| AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT SHALL BE |
| 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 |
| |
| 2. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, |
| SECOND FLOORR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE |
| RATIO AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT |
| SHALL BE 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE |
| 403.1 |
| |
| 3. SHT. LS .1.1 WHAT WILL THE ROOF TERRACE BE USED FOR |
| IF IT IS USED FOR THE RESTAURANT PATRONS FOR DINNING IT |
| SHALL BE CONSIDERED AN A-2 WITH A FIXTURE RATIO OF 1 |
| PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 |
| |
| 4. SHT LS .1.1 FOR THE A-2 RESTAURANT OCCUPANCY A WATER |
| FOUNTAIN IS NOT REQUIRED BUT FOR THE BUSINESS OR |
| MERCANTILE OCCUPANCY'S WITH A OCCUPANT LOAD OVER 15 A |
| WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE 403.1 |
| |
| 5. PLEASE PROVIDE FIXTURE COUNT FOR THE OCCUPANTS OF |
| THE PARK NEXT TO RESTAURANT AND THE STANDARD THAT IT |
| WAS DESIGNED UNDER. PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. SHT LS .1.2 SYSTEM NO-C-AJ-1014 PART OF THE TEXT IS |
| CUT OFF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7. PROVIDE DETAIL WITH A SYSTEM DESIGNED FOR PLASTIC |
| PIPE LARGE THAN 2". PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. SHT. A2-2-2 DETAIL PLEASE SHOW CLEAR FLOOR SPACE FOR |
| WATER CLOSETS. PER FBC ACC 604.3.1 |
| |
| 9. SHT. A2-2-2 LABEL ALL CLEAR FLOR SPACES WITH |
| DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 10.SHT. A2-2-2 THE GRAB BARS SHALL BE MEASURE FROM THE |
| GRIPPING SURFACE TI FINISHED FLOOR. PER FBC ACC 609.4 |
| |
| 11. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| |
| 12. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 604.4 SEATS. |
| THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| |
| 13. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 14. SHT. A8-2-1 DETAIL #3 PLEASE SHOW PLEASE SHOW HOW |
| THE-ROOF DRAIN WILL BE SECURED TO STRUCTURAL SLAB. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 15. SHT. P2.1.1 PROVIDE NOTE ON PLAN OR SHOW ON RISER |
| COMPLIANCE WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THEOUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 16. HOW WILL THE FUTURE CAPPED SANITARY LINE BE |
| LOCATED-UNDER THE SLAB. PER WPB AMEND TO FBC 107.2.1 |
| |
| 17. SHT. P3.2.1 PLEASE SHOW DFU LOAD ON SANITARY |
| ISOMETRIC. PER FBC PL 710.1 AND TABLE 710.1(1) |
| |
| 18. SHT. P3.3.1 THE PIPE SIZE IS MISSING PLEASE CLARIFY |
| PER WPB AMEND TO FBC 107.2.1 |
| A) THE BRANCH FROM SECOND FLOOR TROUGH DRAIN |
| B) THE BRANCH FROM THR RISER CONNECTING TROUGH DRAINS |
| |
| 19. P3.3.1 SQFT IS MISSING ON BRANCH CONNECTING THE |
| ROOF TERRACE TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1 |
| |
| 20. PROVIDE SIZING CALCULATIONS FROM SCHEIR |
| MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 21. SHT. P3.3.1 THE 4" BRANCH CONNECTING THR TRENCH |
| DRAIN-AND A + B STACKS FROM THE ROOF TERRACE IS |
| UNDERSIZED PER FBC PL TABLE 1106.3 |
| |
| 22. SHT. P3.3.1 SHOW SQFT ON OVERFLOW PIPING. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 23. SHT. P3.3.1 THE 6" HORIZONTAL OVERFLOW DRAIN PIPE |
| IS UNDERSIZED PER FBC PL TABLE 1106.3 |
| |
| 24. SHT. P3.3.1 THE SECOND SECTION OF 8" HORIZONTAL |
| DRAIN PIPE WITH 12796 SQFT IS UNDERSIZED PER FBC PL |
| TABLE 1106.3 |
| |
| 25. SHT. P3.3.1 WHAT LEVEL IS THE TRENCH DRAIN THAT IS |
| LABELED WITH 350 SQFT PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 26. SHT. P4.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED |
| AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR |
| A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT. |
| SEE STANDARD DETAIL GS 7 OR GS 7.1 |
| |
| 27. P4.1.1 MIAMI DADE CODES DO NOT APPLY TO THIS |
| PROJECT PLEASE REMOVE ANY REFERENCES FROM PLAN. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 28. P4.2.1 DETAIL WITH SPACING OF PIPE HANGERS DOES NOT |
| COMPLY WITH FBC PL TABLE 308.5 PLEASE CLARIFY |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |