2017-11-28 13:02:07 | 201 NORTH FLAGLER DRIVE |
| PERMIT #17110857 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****APPROVED WITH PROVISIONS***** |
| |
| GENERAL: PLANS INDICATE AN ADDRESS OF 185 BANYAN |
| BOULEVARD; HOWEVER, THE PERMIT APPLICATION INDICATES AN |
| ADDRESS OF 201 NORTH FLAGLER DRIVE. PLEASE COORDINATE |
| THE PROPER ADDRESS. |
| |
| SHEET FP1.1.1: BACKFLOW PREVENTER SHALL BE LOCATED IN |
| ACCORDANCE PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS |
| TO PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION |
| SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE |
| FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| INDICATOR VALVE. |
| (2) A WALL POST INDICATOR VALVE |
| (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| ACCORDANCE WITH SECTION 6.4 |
| (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| THE WALL FACING THE BACKFLOW PREVENTER. |
| (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| ACCESSIBLE FROM THE EXTERIOR |
| (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| AUTHORITY HAVING JURISDICTION |
| |
| SHEET FP1.2.1: A SECOND STANDPIPE RISER WITH FIRE |
| DEPARTMENT HOSE VALVES IS NEEDED ON THE EAST SIDE OF |
| THE BUILDING TO COMPLY WITH THE COVERAGE REQUIREMENTS |
| NFPA 14. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |