Plan Review Notes
Plan Review Notes For Permit 17110857
Permit Number 17110857
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-05 16:37:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. SHEET E1.1.1: PROVIDE AUTOMATIC LIGHTING CONTROL PER
 FBC EC 405.2.2
 3. SHEET E1.2.1: PROVIDE AUTOMATIC LIGHTING CONTROL PER
 FBC EC 405.2.2
 4. SHEET E3.0.0: FEEDER ?F-3? SHOULD NOT HAVE ANY
 EQUIPMENT GROUNDING CONDUCTOR, THIS IS STILL THE
 SERVICE LATERAL AND NOT A FEEDER. NEC 250.6, 250.24,
 250.122
 5. SHEET E3.0.0: MAIN # 1 IS SHOWN AS A DISCONNECT IN
 THE RISER DIAGRAM, BUT IS ALSO SHOWN AS A MAIN LUG
 PANEL IN THE PANEL SCHEDULE. CLARIFY AND/OR CORRECT.
 FBC 107.2.1
 6. SHEET E3.0.0: PANEL ?A? AND PANEL ?PARK? SHOW
 SEVERAL CIRCUITS CONTROLLED THROUGH PHOTOCELL. FBC
 ENERGY STATES: ?LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR A PHOTOSENSOR.? CLARIFY
 WHAT TYPE OF LOAD THIS IS. FBC 107.2.1; FBC EC 405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  