Plan Review Notes
Plan Review Notes For Permit 17110788
Permit Number 17110788
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-21 07:10:452ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
  
 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B
 BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN
 HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52.
 IN REFERENCE TO THE HEIGHT OF THE VANITY BEING A MAX OF
 34? YOU ARE CORRECT THE SECTION THAT I GAVE YOU PG.
 P.52 IN THE MANUAL IS UNDER THE KNEE SPACE FOR A
 FORWARD APPROACH BUT IT REFERENCE THE GUIDELINES AND IN
 THE GUIDELINES UNDER REQUIREMENT 7 USABLE BATHROOMS
 PARAGRAPH (B) SEC (V) IT CALLS OUT FOR THE RIM OF THE
 FIXTURE TO BE A MAX OF 2?10? ABOVE FINISHED FLOOR THE
 KNEE SPACE FOR THE FORWARD APPROACH IS OPTIONAL. THIS
 IS THE WAY THE INSPECTORS HAVE BEEN ENFORCING THIS OUT
 IN THE FIELD ANY DEVIATION FROM THIS SHALL BE APPROVED
 BY THE BUILDING OFFICIAL.
  
  
 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED
 FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB
 AMEND TO FBC 107.2.1
 SHT. P-6.1 DETAILS 4-10 SHOW AIR CHAMBERS WHICH DO NOT
 COMPLY WITH THE CODE. PER FBC PL 604.9
  
 21. SHT. P-4C.1 SHOWS A UNIT A1 IT SHALL SHOW B1, B2A
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 B1 IS STILL MISSING FROM THE SHEET AND B-2A IS ONLY
 SHOWN AS PART OF THE UNIT. B-2 AND B-2A APPEAR TO BE
 THE SAME AND SHOULD USE THE SAME DETAIL.
  
 22. SHT. P5.2 RISER 1 AND 1A PLEASE LABEL 2" P-TRAP ON
 THE GROUND FLOOR UNIT. PER WPB AMEND TO FBC 107.2.1
 IN YOUR RESPONSE YOU REFERENCED WASTE ARMS BUT THAT IS
 NOT WHAT MY COMMENT WAS ADDRESSING I WAS REFERRING TO
 THE 2? P-TRAP NEXT TO THE WC UNDER THE GROUND FLOOR OF
 RISER 1 + 1A IT SHOULD BE A BATH TUB.
  
 NEW COMMENTS:
  
 1. THE SINK IN THE RESIDENTS LOUNGE SHALL COMPLY WITH
 FBC ACC 606.3
  
 2. SHT. P-5.2 RISERS 8 + 8A SHOW A SHOWER THERE IS NO
 SHOWERS SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. SHT P-5.2 RISERS 4, 4A, 6, 6A, 7, 7A, 8 AND 8A ARE
 NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE HUB DRAIN FOR THE ELEVATOR SUMP PUMP SHALL BE
 VENTED PER FBC PL 901.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  