2018-03-21 07:10:45 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH |
| |
| 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B |
| BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN |
| HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52. |
| IN REFERENCE TO THE HEIGHT OF THE VANITY BEING A MAX OF |
| 34? YOU ARE CORRECT THE SECTION THAT I GAVE YOU PG. |
| P.52 IN THE MANUAL IS UNDER THE KNEE SPACE FOR A |
| FORWARD APPROACH BUT IT REFERENCE THE GUIDELINES AND IN |
| THE GUIDELINES UNDER REQUIREMENT 7 USABLE BATHROOMS |
| PARAGRAPH (B) SEC (V) IT CALLS OUT FOR THE RIM OF THE |
| FIXTURE TO BE A MAX OF 2?10? ABOVE FINISHED FLOOR THE |
| KNEE SPACE FOR THE FORWARD APPROACH IS OPTIONAL. THIS |
| IS THE WAY THE INSPECTORS HAVE BEEN ENFORCING THIS OUT |
| IN THE FIELD ANY DEVIATION FROM THIS SHALL BE APPROVED |
| BY THE BUILDING OFFICIAL. |
| |
| |
| 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED |
| FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB |
| AMEND TO FBC 107.2.1 |
| SHT. P-6.1 DETAILS 4-10 SHOW AIR CHAMBERS WHICH DO NOT |
| COMPLY WITH THE CODE. PER FBC PL 604.9 |
| |
| 21. SHT. P-4C.1 SHOWS A UNIT A1 IT SHALL SHOW B1, B2A |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| B1 IS STILL MISSING FROM THE SHEET AND B-2A IS ONLY |
| SHOWN AS PART OF THE UNIT. B-2 AND B-2A APPEAR TO BE |
| THE SAME AND SHOULD USE THE SAME DETAIL. |
| |
| 22. SHT. P5.2 RISER 1 AND 1A PLEASE LABEL 2" P-TRAP ON |
| THE GROUND FLOOR UNIT. PER WPB AMEND TO FBC 107.2.1 |
| IN YOUR RESPONSE YOU REFERENCED WASTE ARMS BUT THAT IS |
| NOT WHAT MY COMMENT WAS ADDRESSING I WAS REFERRING TO |
| THE 2? P-TRAP NEXT TO THE WC UNDER THE GROUND FLOOR OF |
| RISER 1 + 1A IT SHOULD BE A BATH TUB. |
| |
| NEW COMMENTS: |
| |
| 1. THE SINK IN THE RESIDENTS LOUNGE SHALL COMPLY WITH |
| FBC ACC 606.3 |
| |
| 2. SHT. P-5.2 RISERS 8 + 8A SHOW A SHOWER THERE IS NO |
| SHOWERS SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 3. SHT P-5.2 RISERS 4, 4A, 6, 6A, 7, 7A, 8 AND 8A ARE |
| NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 4. THE HUB DRAIN FOR THE ELEVATOR SUMP PUMP SHALL BE |
| VENTED PER FBC PL 901.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |