2018-03-12 10:04:29 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| 2015 5TH EDITION |
| AZOLA WEST PALM BEACH 17110788 |
| |
| SECOND REVIEW: |
| |
| 1. OK ACKNOWLEDGED. |
| ART IN PUBLIC PLACES. |
| |
| 2. NOT ADDRESSED. ELEVATION CERTIFICATE NOT PROVIDED |
| FOR REVIEW. |
| FLOOD ZONE CERTIFICATES |
| FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION |
| 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. |
| AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE |
| BOARD WILL BE REQUIRED OR (2) FREE BOARD DESIGN FLOOD |
| ELEVATION. |
| NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS |
| HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL |
| DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE |
| WITH NAV 88. |
| FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| |
| (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| |
| 3. NOT PROVIDED. |
| |
| PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| |
| 4. THRESHOLD NOTES UNDER SEPARATE THRESHOLD REVIEW |
| STOP. |
| |
| 5. OK DEFFERED SUBMITALS LISTED |
| W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 6. OK ADDRESSED. CONSTRUCTION TRAILERS |
| |
| 7. OK ADDRESSED. |
| PROVIDE AN EVALUATION REPORT FOR SPRAY INSULATION SHOWN |
| ON PAGE A 6.1 KEY NOTE 73 AND FOR RIGID POLY ISO |
| INSULATED BOARD SHOWN ON PAGE A 3.3 KEYNOTE 42. FBC |
| 2603.5.4 |
| |
| 8. OK DEFFERED SUBMITALS LISTED |
| TRUSS ENGINEERING APPROVED BY THE DESIGNER OF RECORD. |
| |
| |
| 9. OK ADRESSED. |
| WELDED OR BOLTED CONNECTIONS |
| |
| 10. OK ADRESSED. |
| SLIDING GLASS DOOR THRESHOLD. |
| |
| 11. OK ADRESSED. |
| PAGE A 9.1 DETAIL 1. FRAMING IS SHOWN AS 24 INCHES ON |
| CENTER. CHECK MANUFACTURER'S SPECIFICATION ON |
| CEMENTITIOUS BOARD. MANY REQUIRE FRAMING AT 16 INCHES |
| ON CENTER. |
| |
| 12. OK ADRESSED. |
| THE SCALE OF 3 INCHES EQUALS 1 FOOT IS NOT ACCURATE |
| PLEASE SEE PAGES A 8.1, A 8.2, A 8.3 AND A 8.4. |
| |
| 13. OK ADRESSED. |
| DETAIL F ON PAGE S 3.3.3 SPECIAL GIRDER TRUSS |
| CONNECTION DETAIL 1, 2, 3 AND 4 ARE MISSING |
| MEASUREMENTS. |
| |
| 14. OK ADRESSED. |
| ON PAGE A 7.3 ELEVATOR NOTE. ELEVATOR SHALL COMPLY WITH |
| FBC 708.14 WAS NOT FOUND. PLEASE UPDATE THIS CODE |
| SECTION. |
| |
| 15. OK ADRESSED. |
| PAGE 8.2 DETAIL 17. PLEASE UPDATE CODE SECTION TO 2014 |
| FBC 5TH EDITION. |
| |
| 16. NOT PROVIDED. |
| PLEASE PROVIDE MANUFACTURE'S SPECIFICATIONS FOR |
| BARBECUES USED. |
| |
| 17. NOT PROVIDED. |
| SEE PAGE A 3.2 DETAIL 3. CUT SECTIONS 4.1 TO 5. THE |
| FOAM OUTLOOKERS ARE OVER 40 FT. SEE ALSO DETAIL 4 AT |
| CUT H FOR ANOTHER EXAMPLE. |
| COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR |
| WALLS. SEE OUTLOOKERS USED AT GABLE ENDS AND DECORATIVE |
| FOAM MEDALLIONS. |
| |
| FBC 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION. |
| ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH |
| THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL |
| COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN |
| HEIGHT ABOVE GRADE PLANE. |
| |
| 18. OK. ADDRESSED. |
| VENT ON TOP OF ELEVATOR SHAFT RATING NOT SHOWN. |
| |
| 19. OK. ADDRESSED. |
| CLARIFY VAPOR BARRIER THAT IS TO BE USED. IT VARIES |
| FROM 6 MIL TO 10 MIL. SEE S 2.1.1.1, S 4.1.1.1, S 4.1.2 |
| AND S 4.1.3 |
| |
| 20. OK. ADDRESSED. |
| EXISTING 2 STORY BUILDING TO BE DEMOLISHED REQUIRES A |
| SEPERATE DEMO PERMIT. FBC 105.1 |
| |
| 21. OK. ADDRESSED. |
| PARKING DETAILS: PARKING LOT STRIPING DETAILS VARY FROM |
| SINGLE TO DOUBLE STRIPING THROUGHOUT THE PLANS. WEST |
| PALM BEACH PARKING LOT STRIPING IS DOUBLE STRIPING. A |
| DETAIL IS AVAILABLE AT THIS DEPARTMENT. NOTE: FC |
| 553.5041(6) HAS CHANGED REGARDING SIGNAGE. THE NEW |
| MINIMUM HEIGHT IS 60 INCHES. |
| |
| 22. OK. ADDRESSED. A SEPARATE REVIEW STOP HAS BEEN |
| ENTERED FOR IMPACT FEES |
| |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |