Plan Review Notes
Plan Review Notes For Permit 17110788
Permit Number 17110788
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-27 18:48:071ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A) SHT. LS-0.0 APPLICABLE CODES-AND GUIDE
 LINES-CHANGE FLORIDA ACCESSIBILITY 2012 TO FBC ACC 2014
 5TH EDITION AND ADD FHA. PER WPB AMEND TO FBC 107.2.1
 B) SHTS. A-5.4 AND A-10.3 THE FHA REQUIRES THAT THE
 COMMON OR PUBLIC USE AREAS COMPLY WITH THE MIN ANSI
 A117.1- 1986 STANDARD OR A MORE RESTRICTIVE
 ACCESSIBILITY STANDARD PLEASE INDICATE ON THE PLAN
 UNDER ACCESSIBILITY NOTES THE STANDARD THAT THE COMMON
 AREAS ARE DESIGNED TO MEET.
  
 2. PROVIDE SIZING CALCULATIONS FOR THE ROOF GUTTERS AND
 DOWN SPOUTS. PER FBC PL TABLE 1106.2(2) AND 1106.6
  
 3. SHT.A-7.2 LEGEND #27 THE ELEVATOR SUMP PIT SHALL BE
 A MIN OF 24" DEEP. PER FBC 712.3.2
  
 4. SHT. A-10.1 UNIT B1 SHOW FHA DESIGN SPEC FOR
 BATHROOMS. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-10.1 UNIT B2 WHAT FHA DESIGN SPEC IS MASTER
 BATH IT IS CALLED OUT AS USABLE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. A-10.2 THIS BUILDING IS NOT REQUIRED TO COMPLY
 WITH FBC ACC 2014 I'M CONFUSED ON WHY YOU HAVE DETAILS
 FOR THIS CODE ON THE PLAN COULD YOU PLEASE CLARIFY THIS
 FOR ME. PER WPB AMEND TO FBC 107.2.1
  
 7.SHT. A-5.4 AND A-10.1 PLEASE PLACE DIMENSIONS ON THE
 CLEAR FLOOR SPACE FOR THE FIXTURES. PER WPB AMEND TO
 FBC 107.2.1
  
 8. SHT. A-10.3 PLEASE PROVIDE THE DIMENSION FOR THE TOP
 OF THE BACKING TO FINISH FLOOR ON THE SHOWER DETAIL
 SHALL BE 38" MIN. PER FHA DESIGN MANUAL REQ. 6 PG. 6.12
  
 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B
 BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN
 HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52
  
 10. SHT. A10.1 PROVIDE DIMENSION BETWEEN APPLIANCES AND
 OPPOSING ELEMENTS IN THE KITCHENS. PER FHA DES MAN REQ
 7 PG.7.7
  
 11. SHT. A-5.4 THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH ANSI A117.1-1986 SEC 4.16.6 FIG 29(B) WITH A MIN
 OF 19" OF THE FLOOR WHICH IS MORE RESTRICTIVE THAN THE
 FBC ACC 2014.
  
 12. THE DRAIN FOR THE ELEVATOR SUMP IS NOT SHOWN ON THE
 SANITARY ISOMETRICS OR THE FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED
 FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB
 AMEND TO FBC 107.2.1
  
 14 PLEASE PLACE NOT ON THE PLAN A SEPARATE PERMIT IS
 REQUIRED FOR THE BACKFLOW ASSEMBLY. PER WPB UTILITIES
 DEPARTMENT
  
 15. SHT. A-5.4 PLEASE PROVIDE THE DIMENSIONS OF THE
 WIDTH AND DEPTH OF THE BATHROOMS. PER WPB AMEND TO FBC
 107.2.1
  
 16. PLEASE PROVIDE OCCUPANT LOAD FOR COVERED PATIO. PER
 WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE PLUMBING FIXTURE LOAD REQUIREMENT
 BREAKDOWN. INCLUDING COVERED PATIO OCCUPANT LOAD. PER
 WPB AMEND TO FBC 107.2.1 AND FBC PL 403.1
  
 18. WILL THESE BE THE BATHROOMS SERVING THE POOL AND
 POOL DECK IF SO PLEASE INCLUDE IN THE PLUMBING FIXTURE
 BREAKDOWN. PER FBC PL 403.1
  
 19. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1
 IT IS NOT SHOWN ON PLUMBING PLAN.
  
 20. SHT. LS-0.1 SHOWS A C1 UNIT NEXT TO THE FITNESS
 CENTER SHT. A-2.1 SHOWS A B1 IN SAME LOCATION-PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 21. SHT. P-4C.1 SHOWS A UNIT A1 IT SHALL SHOW B1, B2A
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 22. SHT. P5.2 RISER 1 AND 1A PLEASE LABEL 2" P-TRAP ON
 THE GROUND FLOOR UNIT. PER WPB AMEND TO FBC 107.2.1
  
 23. SHT. P5.4 THE ISOMETRIC DRAWING FOR THE CUB HOUSE
 BATHROOMS IS CONGESTED AND HARD TO DETERMINE IF VENTED
 PROPERLY PLEASE EXPAND THIS PAT OF THE ISOMETRIC. PER
 WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved