Date |
Text |
2017-12-27 18:48:07 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. A) SHT. LS-0.0 APPLICABLE CODES-AND GUIDE |
| LINES-CHANGE FLORIDA ACCESSIBILITY 2012 TO FBC ACC 2014 |
| 5TH EDITION AND ADD FHA. PER WPB AMEND TO FBC 107.2.1 |
| B) SHTS. A-5.4 AND A-10.3 THE FHA REQUIRES THAT THE |
| COMMON OR PUBLIC USE AREAS COMPLY WITH THE MIN ANSI |
| A117.1- 1986 STANDARD OR A MORE RESTRICTIVE |
| ACCESSIBILITY STANDARD PLEASE INDICATE ON THE PLAN |
| UNDER ACCESSIBILITY NOTES THE STANDARD THAT THE COMMON |
| AREAS ARE DESIGNED TO MEET. |
| |
| 2. PROVIDE SIZING CALCULATIONS FOR THE ROOF GUTTERS AND |
| DOWN SPOUTS. PER FBC PL TABLE 1106.2(2) AND 1106.6 |
| |
| 3. SHT.A-7.2 LEGEND #27 THE ELEVATOR SUMP PIT SHALL BE |
| A MIN OF 24" DEEP. PER FBC 712.3.2 |
| |
| 4. SHT. A-10.1 UNIT B1 SHOW FHA DESIGN SPEC FOR |
| BATHROOMS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. SHT. A-10.1 UNIT B2 WHAT FHA DESIGN SPEC IS MASTER |
| BATH IT IS CALLED OUT AS USABLE PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 6. SHT. A-10.2 THIS BUILDING IS NOT REQUIRED TO COMPLY |
| WITH FBC ACC 2014 I'M CONFUSED ON WHY YOU HAVE DETAILS |
| FOR THIS CODE ON THE PLAN COULD YOU PLEASE CLARIFY THIS |
| FOR ME. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7.SHT. A-5.4 AND A-10.1 PLEASE PLACE DIMENSIONS ON THE |
| CLEAR FLOOR SPACE FOR THE FIXTURES. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 8. SHT. A-10.3 PLEASE PROVIDE THE DIMENSION FOR THE TOP |
| OF THE BACKING TO FINISH FLOOR ON THE SHOWER DETAIL |
| SHALL BE 38" MIN. PER FHA DESIGN MANUAL REQ. 6 PG. 6.12 |
| |
| 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B |
| BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN |
| HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52 |
| |
| 10. SHT. A10.1 PROVIDE DIMENSION BETWEEN APPLIANCES AND |
| OPPOSING ELEMENTS IN THE KITCHENS. PER FHA DES MAN REQ |
| 7 PG.7.7 |
| |
| 11. SHT. A-5.4 THE TOILET PAPER DISPENSER SHALL COMPLY |
| WITH ANSI A117.1-1986 SEC 4.16.6 FIG 29(B) WITH A MIN |
| OF 19" OF THE FLOOR WHICH IS MORE RESTRICTIVE THAN THE |
| FBC ACC 2014. |
| |
| 12. THE DRAIN FOR THE ELEVATOR SUMP IS NOT SHOWN ON THE |
| SANITARY ISOMETRICS OR THE FLOOR PLAN PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED |
| FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 14 PLEASE PLACE NOT ON THE PLAN A SEPARATE PERMIT IS |
| REQUIRED FOR THE BACKFLOW ASSEMBLY. PER WPB UTILITIES |
| DEPARTMENT |
| |
| 15. SHT. A-5.4 PLEASE PROVIDE THE DIMENSIONS OF THE |
| WIDTH AND DEPTH OF THE BATHROOMS. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 16. PLEASE PROVIDE OCCUPANT LOAD FOR COVERED PATIO. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 17. PLEASE PROVIDE PLUMBING FIXTURE LOAD REQUIREMENT |
| BREAKDOWN. INCLUDING COVERED PATIO OCCUPANT LOAD. PER |
| WPB AMEND TO FBC 107.2.1 AND FBC PL 403.1 |
| |
| 18. WILL THESE BE THE BATHROOMS SERVING THE POOL AND |
| POOL DECK IF SO PLEASE INCLUDE IN THE PLUMBING FIXTURE |
| BREAKDOWN. PER FBC PL 403.1 |
| |
| 19. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1 |
| IT IS NOT SHOWN ON PLUMBING PLAN. |
| |
| 20. SHT. LS-0.1 SHOWS A C1 UNIT NEXT TO THE FITNESS |
| CENTER SHT. A-2.1 SHOWS A B1 IN SAME LOCATION-PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 21. SHT. P-4C.1 SHOWS A UNIT A1 IT SHALL SHOW B1, B2A |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 22. SHT. P5.2 RISER 1 AND 1A PLEASE LABEL 2" P-TRAP ON |
| THE GROUND FLOOR UNIT. PER WPB AMEND TO FBC 107.2.1 |
| |
| 23. SHT. P5.4 THE ISOMETRIC DRAWING FOR THE CUB HOUSE |
| BATHROOMS IS CONGESTED AND HARD TO DETERMINE IF VENTED |
| PROPERLY PLEASE EXPAND THIS PAT OF THE ISOMETRIC. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |