2017-12-15 11:21:02 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17110788 |
| 12/15/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC CALCULATIONS ARE INCORRECTLY IDENTIFYING THE |
| PROJECT NAME AS BELLA VITA CLUBHOUSE |
| |
| 2) THE SUBMITTED AC CALCULATIONS DO NOT MEET THE |
| REQUIRED PROCEDURE FOR SYSTEM SIZING AS OUTLINED IN |
| SECTION C407.5.2.3 ENERGY CONSERVATION- MULTIFAMILY |
| RESIDENTIAL BUILDINGS: |
| |
| RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL |
| BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME |
| ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE |
| THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR |
| FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING |
| THESE FEATURES. |
| |
| PLEASE SUBMIT REVISED CALCULATIONS. |
| |
| 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A |
| COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| |
| 4) PROVIDE VENTILATION CALCULATIONS FOR THE APARTMENTS- |
| TABLE 403.3. |
| |
| 5) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| STORAGE ROOMS, AND THE FIRE SERVICE ROOM- TABLE 403.3 |
| |
| 6) PROVIDE ENLARGED AC FLOOR PLAN DRAWINGS FOR THE |
| FITNESS ROOM AND THE LOUNGE. |
| |
| 7) SHEETS M2C.1 & M5.3, PARKING GARAGES:THE EF-2 |
| SCHEDULE INDICATES THE EXHAUST FANS WILL BE ACTIVATED |
| BY THE LIGHT SWITCH. PLEASE SEE SECTIONS 404.1 AND |
| 404.2 AND REVISE THE PLAN TO SHOW THE CORRECT SEQUENCE |
| OF FAN OPERATION AND REQUIRED EXHAUST VENTILATION |
| RATES. |
| |
| 8) M2C.2: A FIRE DAMPER IS REQUIRED FOR THE ELEVATOR |
| SHAFT RELIEF AIR OPENING- SECTION 607.5.2. |
| |
| 9) PLEASE PROVIDE AN ENLARGED DETAIL OF THE ELEVATOR |
| EXHAUST VENTILATION SYSTEM THAT PROVIDES EXHAUST DUCT |
| AND DUCT SUPPORT DETAILS, AND THE EXHAUST DUCT RUN AND |
| TERMIANTION LOCATION INCLUDING REQUIRED CLEARANCES PER |
| SECTIO 501.3.1. |
| |
| 10) M4C.1, UNIT B2: THE 16"X6" RETURN TRANSFER GRILL AT |
| THE MASTER BEDROOM IS UNDERSIZED PER SECTION 601.5 (2) |
| |
| 11) M5.1 & M5.4: PROVIDE THE WIND LOAD DESIGN CRITERIA |
| FOR INSTALLATION OF THE CONDENSERS ON THE STANDS AND ON |
| THE SLABS- SEE SECTION 1609 FBC-14 BUILDING. |
| |
| 12) A5.1: THE DOOR SCHEDULE INDICATES THE AC CLOSET |
| DOORS WILL BE PROVIDED WITH INTUMESCENT PAINT ON THE |
| INTERIOR SIDE IN ORDER TO MEET COMPLIANCE WITH SECTION |
| C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND SECTION |
| 602.2.1 FBC-14 MECHANICAL. PLEASE NOTE THAT THE WPB |
| BUILDING DEPARTMENT WILL NOT PERFORM INSPECTIONS ON THE |
| DOOR, BUT WILL REQUIRE A LETTER FROM THE ENGINEER OF |
| RECORD TO CERTIFY THE APPLICATION OF THE PAINT AND |
| COMPLIANCE WITH THE AFOREMENTIONED CODE SECTIONS. |
| |
| 13) PROVIDE REFRIGERANT PIPING RISER DRAWINGS. |
| |
| 14) REQUIRED SUBMITTALS: |
| FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC |
| STANDS, AC CLIPS, AND THE AIR INTAKE AND EXHAUST OUTLET |
| LOUVERS. |
| RANGE HOODS |
| DRYERS |
| MOTORIZED DAMPERS |
| FIRE DAMPERS |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |