Plan Review Notes
Plan Review Notes For Permit 17110763
Permit Number 17110763
Review Stop G
Sequence Number 1
Notes
Date Text
2017-12-06 04:51:161) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THIS
 ADDRESS. THE PLANS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 2) PERMIT #16020723 SHOWS THE METER AS A 2 PSI GAS
 METER BUT THE SUBMITTED GAS DRAWING SHOWS AN EXISTING
 .5 PSI GAS METER. IF THE METER IS .5 PSI THEN THE
 ENTIRE EXISTING GAS SYSTEM IS UNDERSIZED. IN ADDITION,
 THE TANKLESS WATER HEATER ON YOUR GAS DRAWING IS NOT
 THE ONLY GAS APPLIANCE ON THIS SYSTEM. I SUGGEST YOU
 CONTACT CRAIG MCPHERSON AT 561-805 6684 AND REQUEST A
 COPY OF THE GAS DRAWING FROM PERMIT # 16020723 AND
 SUBMIT TWO COPIES ALONG WITH YOUR GAS DRAWING FOR
 REFERENCE AND ALSO TO USE IN THE SIZING OF THE YOUR
 PIPING FOR THE GENERATOR. EXISTING PIPING MAY HAVE TO
 BE INCREASED IN SIZE TO ACCOMMODATE THE TOTAL BTU LOAD
 ON THE SYSTEM. FBC-FUEL GAS SEC. 401.4.
 3) SHOW THE TYPE OF PIPE AND THE PIPE SIZE OF THE GAS
 LINE COMING FROM THE OULET (CONSUMER SIDE) OF THE GAS
 METER.
 4) A GAS SIZING TABLE FROM THE MANUFACTURER OF THE PE
 PIPE HAS BEEN SUBMITTED FOR A .5 PSI SYSTEM BUT
 PREVIOUS CITY RECORDS SHOW THIS AS A 2 PSI SYSTEM.
 SUBMIT THE CORRECT SIZING TABLE FOR THE PSI OF THE
 SYSTEM. FBC-FUEL GAS SEC.402.3. THE PLANS REFERENCE 3
 DIFFERENT SIZING TABLES. CLARIFY. THE MANUFACTURER'S
 SIZING TABLE IS FOR A PRESSURE DROP OF 6.0 IN. W.C. AND
 THE TABLES REFERENCED ON THE GAS DRAWINGS ARE FOR A
 PRESSURE DROP OF 0.5 IN. W.C. IT CANNOT BE BOTH.
 CLARIFY.
 5) THE GAS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH ONE
 OF THE METHODS IN FBC - FUEL GAS SEC.402.4.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINE
 PRESSURE REGULATOR. FBC- FUEL GAS SEC.410.1.
 7) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4.
 8) THE GENERATOR SPECIFICATIONS NOTE THE BTU LOAD OF
 THE GENERATOR AT FULL LOAD AS 310,000 BTU'S BUT THE GAS
 DRAWING NOTES 288,000 BTU'S. PIPING SYSTEMS SHALL BE
 SIZED TO MEET THE MAXIMUM DEMAND OF THE APPLIANCE.
 FBC-FUEL GAS SEC.402.1.CLARIFY.
  
 NOTE: A CCOMPREHENSIVE PLAN REVIEW COULD NOT BE DONE
 DUE TO THE CONFLICTING PLANS AND INFORMATION PROVIDED.
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved