2017-12-28 12:43:54FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW THE LOCATION OF THE TRANSFORMER AND
 DISCONNECTS AS TO WHERE THE TREES ARE.
  
 PRIMARY TO TRANSFORMER IF NOT WITHIN SIGHT REQUIRES A
 DISCONNECT 450.14
  
 60A BREAKER ON #10 PER WHICH SECTION?
2017-11-27 17:26:32SENT TO ZONING JLEAHY