Plan Review Notes
Plan Review Notes For Permit 17110725
Permit Number 17110725
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-08 16:51:38FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC
 R314.
  
 SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN
 6 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION.
 NEC 210.52; FBC RE3901.2.1
 THIS IS FOR THE SECOND FLOOR BEDROOM
  
 PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC
 210.8; FBC RE3902.2
 PATIO TV OUTLET
  
  