Plan Review Notes
Plan Review Notes For Permit 17110707
Permit Number 17110707
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-13 09:01:09PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE.
 2) MISSING DUCT SIZE ON SUPPLY DUCT IN MASTER
 HALL WAY. SECTION 107 FBC 2014
 3) SEER ON ENERGY CALCULATIONS AND PLAN
 DO NOT MATCH.
  