2017-12-08 15:50:02 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS |
| IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| 2. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| RE3706.2, RE3902 |
| 4. NOTE 11 STATES THAT BEDROOM CIRCUITS SHALL COMPLY |
| WITH 210.12. THIS DOES NOT COVER THE SCOPE OF THIS |
| ARTICLE, WHICH STATES: "ALL 120-VOLT, SINGLE PHASE, 15 |
| AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION." PROVIDE |
| CORRECTION. NEC 210.12; FBC RE3902.12 |
| 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 7. PLAN SHOWS STANDARD RECESS LIGHTS IN LASTER CLOSET. |
| PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. |
| NEC 410.16; FBC RE4003.12 |
| 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |