2017-12-05 06:20:341) SHT. A 102 - SHOW THE WIDTH OF THE SHOWER ON THE 2ND
 FLOOR. THE SHOWER SHALL BE A MINIMUM OF 30 INCHES WIDE
 AND A MINIMUM OF 900 SQUARE INCHES.
 2) SHT. A 102 - THE WATER VALVES FOR THE STACKABLE
 WASHER SHALL BE ACCESSIBLE. FBC-PLUMBING SEC.606.3.
 3) SHT. A113 - INDICATE ON THE PLAN THE SLOPE OF THE 6
 INCH GUTTER. COMPLY WITH FBC-PLUMBING, TABLE 1106.6 FOR
 THE SQUARE FFOOTAGE BEING DRAINED.
 4) THE TANKLESS WATER HEATERS SHALL BE LOCATED A
 MINIMUM OF 4 FEET BELOW OR TO THE SIDE OF A WINDOW OR
 DOOR THAT CAN BE OPENED PERR THE MANUFACTURER'S
 INSTALLATION MANUAL.
 5) AN AIR ARRESTOR IS REQD. ON THE WATER SUPPLY TO THE
 ICE MAKER. FBC-PLUMBING SEC. 604.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  