Plan Review Notes For Permit 17110548 |
Permit Number |
17110548 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-12-05 06:20:34 | 1) SHT. A 102 - SHOW THE WIDTH OF THE SHOWER ON THE 2ND | | FLOOR. THE SHOWER SHALL BE A MINIMUM OF 30 INCHES WIDE | | AND A MINIMUM OF 900 SQUARE INCHES. | | 2) SHT. A 102 - THE WATER VALVES FOR THE STACKABLE | | WASHER SHALL BE ACCESSIBLE. FBC-PLUMBING SEC.606.3. | | 3) SHT. A113 - INDICATE ON THE PLAN THE SLOPE OF THE 6 | | INCH GUTTER. COMPLY WITH FBC-PLUMBING, TABLE 1106.6 FOR | | THE SQUARE FFOOTAGE BEING DRAINED. | | 4) THE TANKLESS WATER HEATERS SHALL BE LOCATED A | | MINIMUM OF 4 FEET BELOW OR TO THE SIDE OF A WINDOW OR | | DOOR THAT CAN BE OPENED PERR THE MANUFACTURER'S | | INSTALLATION MANUAL. | | 5) AN AIR ARRESTOR IS REQD. ON THE WATER SUPPLY TO THE | | ICE MAKER. FBC-PLUMBING SEC. 604.9. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|