Plan Review Notes
Plan Review Notes For Permit 17110548
Permit Number 17110548
Review Stop G
Sequence Number 1
Notes
Date Text
2017-12-06 05:42:511) THE TANKLESS WATER HEATERS SHALL BE LOCATED A
 MINIMUM OF 4 FEET BELOW OR TO THE SIDE OF A WINDOW OR
 DOOR THAT CAN BE OPENED PER THE MANUFACTURER'S
 INSTALLATION MANUAL.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR ALL GAS EQUIPMENT/APPLIANCES. APPLIANCES SHALL BE
 LISTED AND LABELED. FBC-FUEL GAS SEC.301.3.
 3) SHT. P-3 - SHOW THE TYPE OF PIPE AND SIZE OF THE
 PIPE FOR THE TANKLESS WATER HEATERS. FBC -FUEL GAS CODE
 TABLE 402.4 (15).
 4) SHT. P-3 - SHOW THE TYPE OF PIPE AND SIZE FOR THE
 GAS LINE TO THE GENERATOR.
 5) SHOW THE SIZE AND TYPE OF PIPE ON THE OUTLET SIDE OF
 THE GAS METER.
 6) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  