2017-12-13 15:28:58BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OWNER/AGENT TO SIGN ENERGY SUBMITTAL FOR MAIN HOUSE.
 2. REVISIT YOUR WINDOW AND DOOR SCHEDULES AND NOA
 SUBMITTAL PACKAGE. THERE ARE NOA'S MISSING FROM
 SCHEDULES AND NOA'S MISSING FORM SUBMITTAL. I.E. FIXED
 WINDOWS/OHD/ETC.
 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED SURFACE MOUNT
 WIND ABATEMENT SYSTEM.
 4. PROVIDE ICC-ES REPORT FOR PROPOSED ICYNENE
 INSULATION. IDENTIFY PRODUCT TO BE INSTALLED BASED ON
 REQUIRED R - VALUE. PRODUCT MANUFACTURERS INSTALLATION
 INSTRUCTIONS TO BE ON-SITE AT TIME OF INSPECTION.
 5. REF. PLAN PAGE A101 - WIND EXPOSURE AND SURFACE
 ROUGHNESS CATEGORIES SHOULD BE ROUGHNESS B PER FBC
 R301.2.1.4.2 & EXPOSURE B PER R301.2.1.4.3.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 R301.2.1.4.2 SURFACE ROUGHNESS CATEGORIES.
 A GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE (0.79
 RAD) SECTOR SHALL BE DETERMINED FOR A DISTANCE UPWIND
 OF THE SITE AS DEFINED IN SECTION R301.2.1.4.3 FROM THE
 CATEGORIES DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING
 AN EXPOSURE CATEGORY AS DEFINED IN SECTION
 R301.2.1.4.3.
  
 SURFACE ROUGHNESS B. URBAN AND SUBURBAN AREAS, WOODED
 AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED
 OBSTRUCTIONS HAVING THE SIZE OF SINGLE-FAMILY DWELLINGS
 OR LARGER
  
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
  
 EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF HEIGHT OF
 LESS THAN OR EQUAL TO 30 FEET (9144 MM), EXPOSURE B
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 1,500 FEET (457
 M). FOR BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN
 30 FEET (9144 MM), EXPOSURE B SHALL APPLY WHERE SURFACE
 ROUGHNESS B PREVAILS IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 2,600 FEET (792 M) OR 20 TIMES THE
 HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  