2017-12-18 10:51:44 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY GAS | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATION SHEETS FOR THE NATURAL GAS PRESSURE | | REGULATORS. FBC 107.2.1 & 107.3.5.3 | | | | 2) SPECIFY THE TABLE NUMBERS OF THE SPECIFIC GAS SIZING | | TABLES THAT WERE USED TO SIZE THE GAS PIPING SYSTEM. | | FBC 107.2.1 & 107.3.5.3 | | | | |
|