2017-12-13 12:11:51 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN SHOWS STANDARD RECESS LIGHTS IN CLOSETS. PER |
| CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC |
| 410.16; FBC RE4003.12 |
| 2. PROVIDE GFCI PROTECTION FOR POOL PUMP AND POOL SPA |
| PUMP, WHERE APPLICABLE. NEC 680.21(C), 680.44; FBC RE |
| 4203.1.3, 4208.1 |
| 3. NOTE 2 ON SHEET E-003 REFERENCES THE 2008 NEC, WHICH |
| IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| PREFACE, 2011 NEC |
| 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| 107.2.1 |
| 5. GUEST BED #2 DOES NOT SHOW THE REQUIRED SMOKE ALARM. |
| PROVIDE CORRECTION. FBC RE 314.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |