2017-11-15 10:23:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 2 - TWO EXITS ARE INDICATED FROM UNIT # 175, |
| HOWEVER, IT DOES NOT APPEAR THAT THEY MEET THE |
| SEPARATION REQUIREMENTS OF NFPA 101, CHAPTER 39, |
| EXISTING BUSINESS OCCUPANCIES OR CHAPTER 7, MEANS OF |
| EGRESS. |
| |
| THIS IS AN EXISTING BUSINESS OCCUPANCY; HOEVER, DUE TO |
| THE SEPARATION WALL THIS IS NOT AN EXISTING SPACE AND |
| REMOTENESS OF THE TWO EXISTS IS REQUIRED. |
| |
| 39.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 39.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| ACCORDANCE WITH SECTION 7.5. |
| |
| 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| OTHER EMERGENCY CONDITION. |
| |
| 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED |
| IN 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION |
| DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2, |
| SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| AREA TO BE SERVED. |
| |
| PLEASE PROVIDE THE DIMENSIONAL CRITERIA THAT MEETS THE |
| CODE, JUSTIFY WITH CODE REFERNCES OR CORRECT. |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |