Plan Review Notes
Plan Review Notes For Permit 17110463
Permit Number 17110463
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-11-15 10:23:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 2 - TWO EXITS ARE INDICATED FROM UNIT # 175,
 HOWEVER, IT DOES NOT APPEAR THAT THEY MEET THE
 SEPARATION REQUIREMENTS OF NFPA 101, CHAPTER 39,
 EXISTING BUSINESS OCCUPANCIES OR CHAPTER 7, MEANS OF
 EGRESS.
  
 THIS IS AN EXISTING BUSINESS OCCUPANCY; HOEVER, DUE TO
 THE SEPARATION WALL THIS IS NOT AN EXISTING SPACE AND
 REMOTENESS OF THE TWO EXISTS IS REQUIRED.
  
 39.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 39.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH SECTION 7.5.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED
 IN 7.5.1.3.3 THROUGH 7.5.1.3.5.
 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION
 DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2,
 SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED.
  
 PLEASE PROVIDE THE DIMENSIONAL CRITERIA THAT MEETS THE
 CODE, JUSTIFY WITH CODE REFERNCES OR CORRECT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL