Plan Review Notes
Plan Review Notes For Permit 17110463
Permit Number 17110463
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-17 16:30:24 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 561-805-6718 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. PLEASE PROVIDE THE USE OF ROOMS 116 AND 117. THE ONE
 DIMENSION IS LESS THAN 7 FEET.
  
 FBC 1208.1 MINIMUM ROOM WIDTHS.
  
 HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION.
 KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN
 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES
 OR COUNTER FRONTS AND WALLS.
  
 2. IN SUITE 110 THE NEW TENANT SEPARATION WALL HAS LEFT
 THE TWO EXITS WITHIN 13 FT. OF EACH OTHER. THE DIAGONAL
 OF THE SPACE IS APPROXIMATELY 100 FEET. SEE EXCEPTION
 2.
 FBC 1015.2 EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT.
  
 REQUIRED EXITS SHALL BE LOCATED IN A MANNER THAT MAKES
 THEIR AVAILABILITY OBVIOUS. EXITS SHALL BE UNOBSTRUCTED
 AT ALL TIMES. EXIT AND EXIT ACCESS DOORWAYS SHALL BE
 ARRANGED IN ACCORDANCE WITH SECTIONS FBC 1015.2.1 AND
 1015.2.2.
  
 FBC 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR
 EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART
 EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 EXIT DOORS OR EXIT ACCESS DOORWAYS. INTERLOCKING OR
 SCISSOR STAIRS SHALL BE COUNTED AS ONE EXIT STAIRWAY.
  
 EXCEPTIONS: 2. WHERE A BUILDING IS EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION FBC 903.3.1.1 OR 903.3.1.2, THE SEPARATION
 DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS
 SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  