| ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| 561-805-6718 [email protected] |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION |
| |
| 1. PLEASE PROVIDE THE USE OF ROOMS 116 AND 117. THE ONE |
| DIMENSION IS LESS THAN 7 FEET. |
| |
| FBC 1208.1 MINIMUM ROOM WIDTHS. |
| |
| HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT |
| LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION. |
| KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN |
| 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES |
| OR COUNTER FRONTS AND WALLS. |
| |
| 2. IN SUITE 110 THE NEW TENANT SEPARATION WALL HAS LEFT |
| THE TWO EXITS WITHIN 13 FT. OF EACH OTHER. THE DIAGONAL |
| OF THE SPACE IS APPROXIMATELY 100 FEET. SEE EXCEPTION |
| 2. |
| FBC 1015.2 EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT. |
| |
| REQUIRED EXITS SHALL BE LOCATED IN A MANNER THAT MAKES |
| THEIR AVAILABILITY OBVIOUS. EXITS SHALL BE UNOBSTRUCTED |
| AT ALL TIMES. EXIT AND EXIT ACCESS DOORWAYS SHALL BE |
| ARRANGED IN ACCORDANCE WITH SECTIONS FBC 1015.2.1 AND |
| 1015.2.2. |
| |
| FBC 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS. |
| WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED |
| FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR |
| EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART |
| EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| EXIT DOORS OR EXIT ACCESS DOORWAYS. INTERLOCKING OR |
| SCISSOR STAIRS SHALL BE COUNTED AS ONE EXIT STAIRWAY. |
| |
| EXCEPTIONS: 2. WHERE A BUILDING IS EQUIPPED THROUGHOUT |
| WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION FBC 903.3.1.1 OR 903.3.1.2, THE SEPARATION |
| DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS |
| SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH OF THE |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. |
| |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |
| |