Plan Review Notes
Plan Review Notes For Permit 17110434
Permit Number 17110434
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-21 13:53:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110434
 11/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGY
 COMPLIANCE FORM R405-2014.
  
 2) THE SUBMITTED ENERGY FORM R405-2014 INDICATES LOW-E
 WINDOWS THROUGHOUT THE RESIDENCE, HOWEVER THERE IS NO
 RECENT PERMIT ON FILE FOR THE WINDOWS. PLEASE CLARIFY
 HOW THE U-FACTORS AND SHGC OF THE WINDOWS WERE
 DETERMINED.
  
 3) AN ELECTRICAL PLAN IS SUBMITTED, HOWEVER IT IS NOT
 CLEAR IF THE COST OF THE ELECTRICAL IS INCLUDED IN
 $6800.00 VALUE ON THE APPLICATION. PLEASE CLARIFY AND
 SUBMIT AN ELECTRICAL SUB-PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  