2017-12-04 11:41:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110427
 12/4/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE AC PLAN INDICATES A TOTAL OF 1420
 CFMS OF CONDITIONED AIR TO BE SUPPLIED BY THE 3.0-TON
 SYSTEM. PROVIDE PRODUCT DATA FROM THE AC MANUFACTURER
 TO CONFIRM THE SYSTEM CAN SUPPLY THAT MUCH AIR.
  
 2) M-1: PROVIDE A PRODUCT DATA SHEET FOR THE 3" FLEX
 DUCT. TYPICALLY, THE SMALLEST FLEX DUCT AVAILABLE IS A
 4"
  
 3) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE
 FORM R405-2014.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER