2017-12-07 09:01:02 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO SETS OF A DRAINAGE PLAN WITH ELEVATIONS |
| TO SHOW COMPLIANCE WITH FBC-R401.3. SURFACE DRAINAGE |
| SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER |
| APPROVED POINT OF COLLECTION THAT DOES NOT CREATE A |
| HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE WATER |
| AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL A |
| MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET |
| (3048 MM). EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR |
| OTHER PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF |
| FALL WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL |
| BE CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE |
| STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) |
| OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| 2 PERCENT AWAY FROM THE BUILDING. |
| THIS INFORMATION IS REQUIRED ON THE SITE PLAN PER FBC |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, |
| FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD |
| ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| ACCURATE BOUNDARY LINE SURVEY. |
| IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL SHOW |
| CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND SIZE |
| OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE TO |
| REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS |
| AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A |
| SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR |
| ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED. |
| |
| 2) SPECIFY THE SIZE OF THE ATTIC ACCESS ON THE PLANS. |
| FBC-R807.1 ATTIC ACCESS, THE ROUGH-FRAMED OPENING SHALL |
| NOT BE LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762 |
| MM) AND SHALL BE LOCATED IN A HALLWAY OR OTHER READILY |
| ACCESSIBLE LOCATION. |
| |
| 3) ON SHEET 4 - 4 OF THE PLANS, THE ROOF FRAMING PLAN |
| SPECIFIES (2) SIMPSON HETAL 20 ANCHORS FOR THE GIRDER |
| TRUSS WITH AN UPLIFT OF 3600 LBS. THIS IS NOT CORRECT. |
| THE SIMPSON CATALOG HAS AN UPLIFT LOAD CAPACITY OF 2700 |
| LBS. FOR (2) HETA ANCHORS ON A TWO PLY TRUSS. PLEASE |
| CORRECT. |
| |
| |