2017-11-14 08:45:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R310.1 REQUIRES EVERY SLEEPING ROOM TO HAVE AT
 LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING.
 IN ORDER TO VERIFY THIS REQUIREMENT, PROVIDE A FLOOR
 PLAN WITH THE ROOMS LABELED. SPECIFY THE TYPE AND SIZE
 OF THE EXISTING WINDOWS ON THE PLANS. IF WINDOWS ARE
 CONNECTED TO EACH OTHER USING MULLIONS SPECIFY THE SIZE
 AND NUMBER OF THE WIDOWS IN THE OPENING. FBC 107.2.1
  
 2) A PRODUCT APPROVAL FOR STRUCTURAL MULLIONS WAS
 SUBMITTED. INDICATE THE CONFIGURATION OF THE WIDOWS
 WEAR THIS WILL BE INSTALLED. IN ORDER TO REVIEW THE
 MULLIONS FOR CODE COMPLIANCE THE MULLION SPAN AND
 TRIBUTARY WIDTH ARE REQUIRED.FBC - R301.2.1
  
 3) THE PRODUCT CERTIFICATION AND INSTALLATION
 INSTRUCTIONS THAT ARE ATTACHED TO THE HORIZONTAL
 SLIDING WINDOW FL16804 ARE NOT THE ONES FOR THE XO, OX
 CONFIGURATIONS THAT WERE CIRCLED BY YOU ON PAGE 2 OF
 THE PRODUCT APPROVAL. PLEASE CORRECT. FBC 107.2.1
  
  