Plan Review Notes
Plan Review Notes For Permit 17110377
Permit Number 17110377
Review Stop G
Sequence Number 2
Notes
Date Text
2018-03-13 05:41:161) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS
 SUBMITTAL PACKAGE. ONE SHOWS AN EXISTING GAS SYSTEM AND
 GAS METER TO WHICH THE GAS LINE FOR THE GENERATOR IS
 CONNECTED AND THE OTHER SHOWS A NEW GAS METER DEDICATED
 TO THE GENERATOR. IN ADDITION, THE GAS PERMIT
 APPLICATION DESCRIPTION OF WORK STATES "TIE INTO
 EXISTING NG METER FOR GENERATOR INSTALL." ALSO, THE
 RESPONSE LETTER FROM APS STATES THAT THIS IS A NEWW
 NATURAL GAS LINE FROM THE METER TO THE GENERATOR ONLY.
 NO OTHER APPLIANCES ARE ON THIS LINE WITH THE
 GENERATOR. AT THIS POINT, I HAVE NO IDEA WHAT IS BEING
 DONE OR HOW DUE TO THE CONFLICTING PLANS AND
 INFORMATION THAT HAS BEEN SUBMITTED. CLARIFY.
 2) REMOVE ALL OLD PLANS AND DOCUMENTS FROM THIS
 SUBMITTAL AND SUBMIT TWO COMPLETE SETS OF PLANS THAT
 CLEARLY REFLECT THE SCOPE OF PROPOSED WORK TO BE DONE.
 WPB AMEND. TO FBC SEC. 107.1, 107.2.1.
 3) THE REGULATOR SPECIFICATIONA THAT HAVE BEEN
 SUBMITTED ARE FOR SERVICE REGULATORS WHICH ARE
 INSTALLED BY THE GAS SUPPLIER. ARE YOU USING THESE AS
 THE 2ND STAGE REGULATOR AT THE GENERATOR? CLARIFY.
 4) SHEET P1 IS BECOMING DIFFICULT TO READ IN AREAS WITH
 SMALL PRINTING. SUBMIT TWO COPIES OF A CLEAR AND
 LEGIBLE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  