2017-11-27 15:16:49 | 11-27-2017 1ST GAS REVIEW**DENIED** |
| |
| 1) MISSING SCH 40 METALLIC SIZING TABLE. SUBMIT TWO |
| COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE THE |
| GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, |
| 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, |
| G2413.2, & G2413.3. |
| |
| 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1. |
| |
| 3) CITY RECORD SHOWS EXISTING GAS SYSTEM. THE BTU LOAD |
| OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL |
| BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |
| [email protected] |
| |
| |
| |
| |