2017-11-27 15:01:05 | 11-27-2017 1ST GAS REVIEW**DENIED** |
| |
| 1) YOUR GAS RISER / ISOMETRIC CONFLICTS WITH CITY |
| RECORDS. YOUR TOTAL P.E IS LISTED AS 40" BUT CITY |
| RECORDS SHOWS 125' . ALSO CITY RECORDS SHOW THE FURTURE |
| GENERATOR SIZE AS 500,000BTU BUT YOUR PROPOSING A |
| 750,000 BTU GENERATOR. PROVIDE A COMPLETE RISER/ |
| ISOMETRIC ON THE COMPLETE GAS SYSTEM.FGC SECS. 401.4, |
| 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, |
| G2412.8, G2413.1, G2413.2, G2413.3 |
| |
| 2) PROVIDE CORRECT FUEL TABLE OF SCH 40 METALLIC PIPING |
| FOR .5LB. SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 |
| FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES |
| 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. |
| G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| |
| 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1 |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |