2017-12-07 05:14:27 | 1.) NOTE ON THE PLANS THE TYPE AND SIZE OF THE PIPE ON |
| THE OUTLET OF THE GAS METER. PIPE SHALL BE SIZED FOR |
| THE TOTAL BTU LOAD OF THE SYSTEM INCLUDING FUTURE |
| APPLIANCES. FBC-FUEL GAS SEC.402.2. |
| 2) SHOW THE SIZE AND TYPE OF PIPE DOWNSTREAM OF EACH |
| PRESSURE REGULATOR AT EACH APPLIANCE. |
| 3) SHOW THE DISTANCE FROM EACH PRESSURE REGULATOR TO |
| THE APPLIANCE. IF ALL ARE LESS THAN 10 FEET INDICATE SO |
| ON THE PLANS. |
| 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| G2412.8, G2413.1, G2413.2, & G2413.3.YOU HAVE SUBMITTED |
| A COPY OF THE TABLE FOR THE PE BUT WHAT ABOUT THE LOW |
| PRESSURE SYSTEM? THE TYPE OF PIPING BEING USED FOR THE |
| LOW PRESSURE SYSTEM IS NOT EVEN NOTED ON THE PLANS SO A |
| COMPLETE REVIEW COULD NOT BE DONE. 2ND REQUEST. |
| 5) SIZE THE PE BRANCHES TO THE BBQ AND THE FUTURE |
| STOVE. |
| 6) REGULATORS INSTALLED OUTDOORS SHALL BE APPROVED FOR |
| EXTERIOR USE. FBC-FUEL GAS SEC.410.1. MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION INSTRUCTIONS SHALL BE |
| ONSITE FOR FINAL INSPECTION. FBC FUEL GAS SEC.410.1, |
| 305.1. |
| 7) FUTURE OUTLETS FOR APPLIANCES SHALL BE EQUIPEED WITH |
| A LISTED SHUTOFF VALVE, A LINE PRESSURE REGULATOR AND A |
| PLUG OR NIPPLE AND CAP. |
| NOTE** THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES |
| / EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| |