Plan Review Notes
Plan Review Notes For Permit 17110362
Permit Number 17110362
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-14 04:41:151) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE
 SUBMITTED DOCUMENTS DO NOT SHOW THIS DEVICE IS LEAD
 FREE. THE 975 XL2 IS LEAD FREE BUT NOT THIS DEVICE.
 2014 FBC-PLUMBING SEC.605.2.1 AND CITY OF WEST PALM
 BEACH MANUAL FOR CROSS CONNECTION CONTROL.
 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 CITY OF WEST PALM BEACH MANUAL FOR CROSS CONNECTION
 CONTROL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  