2017-11-09 12:11:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT (2 STORY STRUCTURE) AND
 THE ROOF SLOPE OF THE STRUCTURE. FBC 107.2.1,
 FBC-R301.2.1
  
 2) THIS TWO STORY STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY D WITH A 170 MPH WIND SPEED. THE PRODUCT
 APPROVAL THAT WAS SUBMITTED FOR THE METAL ROOFING HAS A
 MAXIMUM UPLIFT DESIGN PRESSURE OF -71 PSF. THIS UPLIFT
 IS NOT ADEQUATE FOR THE REQUIRED UPLIFT PRESSURES IN
 THE PERIMETER AND CORNER ROOF AREAS. FBC-R301.2.1