2017-11-09 12:11:33 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE MEAN ROOF HEIGHT (2 STORY STRUCTURE) AND | | THE ROOF SLOPE OF THE STRUCTURE. FBC 107.2.1, | | FBC-R301.2.1 | | | | 2) THIS TWO STORY STRUCTURE IS LOCATED IN EXPOSURE | | CATEGORY D WITH A 170 MPH WIND SPEED. THE PRODUCT | | APPROVAL THAT WAS SUBMITTED FOR THE METAL ROOFING HAS A | | MAXIMUM UPLIFT DESIGN PRESSURE OF -71 PSF. THIS UPLIFT | | IS NOT ADEQUATE FOR THE REQUIRED UPLIFT PRESSURES IN | | THE PERIMETER AND CORNER ROOF AREAS. FBC-R301.2.1 |
|