Plan Review Notes
Plan Review Notes For Permit 17110324
Permit Number 17110324
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-14 05:12:261) INDICATE ON THE PLAN IF ANY OF THE WALLS BEING
 REPAIRED ARE FIRE RATED WALLS. IF SO, THE FIRE RATING
 OF THE WALL SHALL NOT BE COMPROMISED. SUBMIT TWO COPIES
 OF A LISTED FIRE RATED WALL DETAIL FOR REVIEW.WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) INDICATE THE MATERIAL FOR THE TILE BASE IN THE
 SHOWER ON THE PLAN. COMPLY WITH FBC SEC. 2509.2.
 WATER-RESISTANT GYPSUM BACKIN G BOARD SHALL NOT BE USED
 IN SHOWER OR BATHTUB AREAS. FBC SEC.2509.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW