2017-11-17 16:25:061ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #17110321
 11/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES
  
 3) M2.1: PLEASE CLARIFY IF THE VAV BOX BY ROOM 105 IS
 NEW OR EXISTING.
  
 4) INDICATE IF THERE ARE ANY COOKING APPLIANCES IN THE
 NEW CAFE AND PROVIDE EXHAUST VENTILATION WHERE
 REQUIRED.
  